Skip to main content
Siemens 3VA2325-5HM32-0BK0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2325-5HM32-0BK0 Circuit Breaker, 55kA @ 415V, 250

MPN3VA2325-5HM32-0BK0

Siemens 3VA2 IEC frame 400, breaking capacity class M, 3-pole circuit breaker, Icu=55kA @ 415V, with ETU330 LIG electronic trip unit, In=250A, overload Ir=100-250A, short-circuit Ii=1.5-12xIn, ground-fault Ig=0.2-1xIn, tg=0.1/0.3s, includes undervoltage release 24V DC, auxiliary and alarm switches.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Product details

The 3VA2325-5HM32-0BK0 is a Siemens 3VA2 IEC frame 400 molded case circuit breaker with a breaking capacity class M rating of Icu=55kA at 415V AC. The 3-pole construction suits three-phase line protection. The ETU330 electronic trip unit provides LIG protection: Long-time (overload) adjustable Ir=100A to 250A, Instantaneous (short-circuit) adjustable Ii=1.5 to 12 times In, and Ground-fault protection with adjustable Ig=0.2 to 1 times In and time delay tg=0.1 or 0.3 seconds. This selectivity suite lets you coordinate downstream breakers and minimize nuisance trips on transient faults.

Accessories and deployment context

The UVR ensures the breaker trips on loss of control voltage — a standard safety interlock for emergency-stop circuits or undervoltage protection on motor feeders. The auxiliary and alarm contacts feed status back to a PLC or SCADA for remote indication. Mounts in standard IEC panelboard or switchgear cubicle; the frame 400 footprint is common across the 3VA2 family, so retrofitting an existing installation with this unit typically requires no busbar rework.

Frequently asked questions

Where can I buy 3VA2325-5HM32-0BK0 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

What protection functions does the ETU330 LIG trip unit provide?

The ETU330 LIG provides Long-time overload protection (Ir adjustable 100A to 250A), Instantaneous short-circuit protection (Ii adjustable 1.5 to 12 x In), and Ground-fault protection (Ig adjustable 0.2 to 1 x In, with time delay tg selectable 0.1 or 0.3 seconds).

What is the breaking capacity of this breaker?

The 3VA2325-5HM32-0BK0 carries an Icu rating of 55kA at 415V AC, classified as breaking capacity class M under the IEC 3VA2 frame.

MPN
3VA2325-5HM32-0BK0