The 3VA2325-5HN32-0HL0: Breaking capacity is 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V — these figures govern selectivity coordination with downstream devices. The continuous current holds at 250 A up to 50 °C ambient, then derates to 240 A at 55 °C, 235 A at 60 °C, 230 A at 65 °C, and 225 A at 70 °C. Maximum power loss is 37.5 W.
Trip unit and auxiliary configuration
Fitted with an ETU350 electronic overcurrent release. A shunt trip release (STL) is integrated for remote tripping.
Physical dimensions and environment
Dimensions: 248 mm height, 138 mm width, 110 mm depth. The part is designed for panel-mount installation typical of SENTRON MCCBs.