Skip to main content
Siemens 3VA2325-5HN32-0KC0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2325-5HN32-0KC0 MCCB, 250 A, 3-Pole

MPN3VA2325-5HN32-0KC0

Siemens SENTRON molded case circuit breaker, 3VA2 series, order code 3VA2325-5HN32-0KC0, 250 A continuous rating, 3-pole, line protection design, with shunt trip and 2 auxiliary switches HQ.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2325-5HN32-0KC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2325-5HN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2325-5HN32-0KC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C250 A
Current at 60 °C250 A
Current at 65 °C250 A
Current at 70 °C250 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.37.5 W

Protection & Trip Unit

3VA2325-5HN32-0KC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2325-5HN32-0KC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2325-5HN32-0KC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2325-5HN32-0KC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2325-5HN32-0KC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

What this MCCB is and what it carries

The Siemens SENTRON 3VA2325-5HN32-0KC0 is a 3-pole molded case circuit breaker (MCCB) rated for 250 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed in a warm enclosure. Breaking capacity is 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 7.5 kA at 690 V, which gives you headroom for high-fault industrial services without cascading upstream. This variant is configured for line protection with a shunt trip (STL) release and two HQ auxiliary switches built in. No undervoltage release, no ground-fault monitoring, no communication module — it's a straightforward power breaker.

Panel fit and thermal budget

Dimensions are 248 mm high, 138 mm wide, 110 mm deep — standard SENTRON 3VA2 footprint for a 250 A frame. Mounts on a DIN rail or panel-mount plate; verify gland-plate clearance for the 110 mm depth in shallow enclosures. Maximum power loss is 37.5 W, which factors into enclosure thermal calculations if you're stacking multiple breakers in a sealed cabinet. Operating temperature range is -25 °C to 70 °C; storage from -40 °C to 80 °C. The breaker is rated to run at its full 250 A even at 70 °C ambient, so no derating curve to chase for most industrial environments.

Frequently asked questions

What is the breaking capacity of 3VA2325-5HN32-0KC0 at 480 V?

The evidence gives 121 kA at 415 V and 440 V, and 75.6 kA at 500 V. At 480 V the value would fall between those two points; for exact coordination consult the selectivity tables from Siemens.

Where can I buy 3VA2325-5HN32-0KC0 and how is it quoted?

This part is sourced to order through independent distribution. Submit an RFQ for current availability and pricing — stock and lead time are confirmed at quote time.

Does 3VA2325-5HN32-0KC0 include a shunt trip or undervoltage release?

It includes a shunt trip (STL) release and two HQ auxiliary switches. It does not have an undervoltage release or ground-fault monitoring.

MPN
3VA2325-5HN32-0KC0