Motor-protection MCCB for 250 A feeder circuits
Breaking capacity is 187 kA at 240 V AC, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 7.5 kA at 690 V. At 415 V the 121 kA rating still exceeds most panelboard SCCR requirements, so selectivity with upstream breakers is achievable without oversizing.
Integration and panel fit
Three-pole construction with a 138 mm width, 248 mm height, and 110 mm depth. For applications that need shunt trip or ground-fault, the 3VA2 platform supports those as auxiliary releases, but this specific order code omits them.