Skip to main content
Siemens 3VA2325-5MN32-0DF0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2325-5MN32-0DF0 SENTRON MCCB, 250 A, 3-Pole, Moto

MPN3VA2325-5MN32-0DF0

Siemens SENTRON 3VA series molded case circuit breaker, 3VA2325-5MN32-0DF0, 3-pole, 250 A, motor protection design, with undervoltage release and auxiliary switches, 110 mm depth, 138 mm width, 248 mm height.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2325-5MN32-0DF0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.#BEZUG!
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2325-5MN32-0DF0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C250 A
Current at 60 °C250 A
Current at 65 °C250 A
Current at 70 °C250 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.40 W

Protection & Trip Unit

3VA2325-5MN32-0DF0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2325-5MN32-0DF0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2325-5MN32-0DF0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2325-5MN32-0DF0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2325-5MN32-0DF0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

The Siemens 3VA2325-5MN32-0DF0 is a SENTRON molded case circuit breaker (MCCB) designed for motor protection, rated at 250 A continuous at 40 °C across the full 3-pole set — no derating needed up to 70 °C, which simplifies panel layout in warm enclosures. Breaking capacity is 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 7.5 kA at 690 V — high enough for most industrial fault-current scenarios, though the 690 V figure means it is not a primary choice for 690 V mains without careful coordination study. This breaker includes an undervoltage release (UVR) and one auxiliary switch plus one trip alarm switch HQ, plus phase failure detection — it drops the load on loss of phase or undervoltage, which is standard for motor protection circuits that need to prevent single-phasing. Power loss is 40 W maximum at rated current — modest for a 250 A frame, but worth accounting for in a sealed panel with other heat sources.

Integration and Mounting

The breaker measures 110 mm deep, 138 mm wide, and 248 mm high — a standard 3-pole MCCB footprint that fits most 250 A frame panels without modification. Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C — suitable for unconditioned enclosures in most industrial environments. The undervoltage release and auxiliary switches are factory-integrated, reducing field wiring and panel-builder labor compared to adding them as external modules.

Frequently asked questions

Does this breaker include phase failure detection?

Yes, phase failure detection is built in, along with an undervoltage release — the breaker will trip on loss of any phase or undervoltage condition.

MPN
3VA2325-5MN32-0DF0