Skip to main content
Siemens 3VA2325-5MN32-0KH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2325-5MN32-0KH0 SENTRON MCCB, 250 A, 3-Pole, Moto

MPN3VA2325-5MN32-0KH0

Siemens SENTRON 3VA series, molded case circuit breaker (MCCB), 3VA2325-5MN32-0KH0, 3-pole, 250 A, motor protection design, 187 kA interrupting at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2325-5MN32-0KH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2325-5MN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2325-5MN32-0KH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C250 A
Current at 60 °C250 A
Current at 65 °C250 A
Current at 70 °C250 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.37.5 W

Protection & Trip Unit

3VA2325-5MN32-0KH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2325-5MN32-0KH0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2325-5MN32-0KH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2325-5MN32-0KH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2325-5MN32-0KH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

SENTRON 3VA2325-5MN32-0KH0 — 250 A Motor Protection MCCB

The Siemens 3VA2325-5MN32-0KH0 is a SENTRON-series molded case circuit breaker (MCCB) designed specifically for motor protection, with a full 250 A rating that holds flat across the entire 40 °C to 70 °C ambient range — no derating curve to manage in a warm panel. Three-pole construction with phase failure detection built in, plus a shunt trip (STL) auxiliary release and a 2-auxiliary-switch + 1 trip alarm switch configuration (HQ) for status feedback to a PLC or safety relay. Interrupting capacity hits 187 kA at 240 V, 121 kA at 415/440 V, 75.6 kA at 500 V, and 7.5 kA at 690 V — that 187 kA figure means it can sit upstream of a high-fault transformer secondary without needing a current-limiting fuse ahead of it.

Panel Fit and Mounting

Footprint is 138 mm wide × 248 mm tall × 110 mm deep — a standard 3-pole MCCB envelope that fits existing SENTRON 3VA cutouts and busbar systems without re-drilling the backplate. The basic switch variant is 3VA2325-5MN32-0AA0; this order code adds the shunt trip and auxiliary switch block, so the depth clearance needs to accommodate the STL actuator — 110 mm is the installed depth with the aux block fitted.

Specs That Matter for the BOM Line

Power loss at rated load is 37.5 W maximum — relevant for thermal budgeting in a sealed enclosure; the trip indicator and voltage trigger are present, so you get local visual trip indication and a remote signal without an add-on module. Operating temperature range is -25 °C to +70 °C, storage from -40 °C to +80 °C — the 70 °C operating ceiling matches the flat 250 A rating, so no derating needed even at the top of the band. Short-time delay adjustable from 4 s minimum to 17 s maximum — this is the I²t withstand time for selective coordination downstream; a 17 s delay lets downstream breakers clear before this unit trips, keeping the rest of the bus live.

Frequently asked questions

What is 3VA2325-5MN32-0KH0's listed depth?

The installed depth is 110 mm (4.33 in) with the shunt trip and auxiliary switch block fitted.

MPN
3VA2325-5MN32-0KH0