Skip to main content
Siemens 3VA2325-6HK42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2325-6HK42-0AA0 SENTRON MCCB, 250 A, 4-Pole, ETU3

MPN3VA2325-6HK42-0AA0
Active

Siemens SENTRON 3VA2325-6HK42-0AA0, molded case circuit breaker (MCCB), 4-pole, Line protection, 250 A rated continuous current Iu, ETU340 overcurrent release, breaking capacities 242 kA at 240 V / 187 kA at 415 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2325-6HK42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA2325-6HK42-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C242.5 A
Current at 60 °C237.5 A
Current at 65 °C230 A
Current at 70 °C220 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V11 kA
Power loss, max.37.5 W

Protection & Trip Unit

3VA2325-6HK42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU340

Construction & Connection

3VA2325-6HK42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2325-6HK42-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2325-6HK42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-40 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2325-6HK42-0AA0 — Mechanical
ParameterValue
Height248 mm
Width184 mm
Depth110 mm
Height (in)9.8 in
Width (in)7.2 in
Depth (in)4.3 in

Product details

What this MCCB carries — and what it means for the panel

The Siemens 3VA2325-6HK42-0AA0 is a 4-pole SENTRON molded case circuit breaker (MCCB) rated for 250 A continuous current at 40 °C, carrying the ETU340 electronic trip unit. Line protection version — no ground-fault monitoring, no communication module. The 242 kA breaking capacity at 240 V tells you this breaker can interrupt very high fault currents at that voltage, which matters for main incoming feeders in industrial switchboards where the upstream transformer can deliver that kind of energy. At 415 V the rating holds at 187 kA, and at 690 V it drops to 11 kA — a steep derate that reflects the arc-extinction physics in air at higher voltage. The 800 V rated insulation voltage (Ui) confirms it is designed for 690 V systems with margin.

Current derating — the real-world continuous rating

Full 250 A is available up to 50 °C ambient. Above that the unit derates linearly: 242.5 A at 55 °C, 237.5 A at 60 °C, 230 A at 65 °C, and 220 A at 70 °C. If your panel internal temperature runs hot — say a non-ventilated enclosure near a dryer section or a crowded MCC lineup — the 55 °C or 60 °C figure is the one to size against, not the 40 °C nameplate. The 37.5 W maximum power loss is the heat the breaker dumps into the enclosure; factor it into your thermal budget.

Trip unit and selectivity

The ETU340 is an electronic overcurrent release with adjustable N-conductor protection (OFF, 50%, or 100%). The thermal memory and long-time pickup settings (tr min and tr max both listed at 1500) are part of the coordination toolkit for achieving selective tripping downstream. For a mill electrical engineer building a selective coordination study, the ETU340 gives you the adjustability to hold in through motor-start inrush while clearing a bolted fault on a branch feeder. The 20 000 mechanical endurance cycles are adequate for a main or feeder breaker that sees infrequent operation — not a switching duty device.

Mounting and integration

Dimensions: 248 mm high, 184 mm wide, 110 mm deep. IP40 on the front — suitable for a dry indoor panel, not for washdown. The 4-pole form factor (3 phases plus switched neutral) is standard for TN-S or TN-C-S systems where the neutral needs to be isolated and protected. Bolts into a fixed mounting plate or a withdrawable cradle depending on the SENTRON 3VA system frame.

Frequently asked questions

Where can I buy 3VA2325-6HK42-0AA0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA2325-6HK42-0AA0 at 415 V?

187 kA at 415 V, and the same rating applies at 440 V. At 240 V it reaches 242 kA; at 500 V it drops to 121 kA; at 690 V it is 11 kA.

What trip unit does 3VA2325-6HK42-0AA0 use?

The ETU340 electronic overcurrent release, with adjustable N-conductor protection (OFF, 50%, 100%) and fixed long-time settings (tr min and tr max both 1500).

MPN
3VA2325-6HK42-0AA0