Skip to main content
Siemens 3VA2325-6HL32-0AC0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2325-6HL32-0AC0 MCCB, 250 A, 3-Pole, 110

MPN3VA2325-6HL32-0AC0

Siemens SENTRON 3VA2 series molded case circuit breaker, 3VA2325-6HL32-0AC0, 250 A, 3-pole, line protection, 110 mm depth.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2325-6HL32-0AC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2325-6HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2325-6HL32-0AC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C250 A
Current at 60 °C250 A
Current at 65 °C250 A
Current at 70 °C250 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.37.5 W
3VA2325-6HL32-0AC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2325-6HL32-0AC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2325-6HL32-0AC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2325-6HL32-0AC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2325-6HL32-0AC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

It carries a maximum breaking capacity of 242 kA at 240 V and 187 kA at 415 V, with derating to 7.5 kA at 690 V — the SCCR headroom at typical industrial voltages (240–480 V) is substantial, so it can be applied upstream of smaller branch breakers without coordination concerns.

Current rating and thermal performance

That is unusual for a compact-frame MCCB; many competitors start tapering above 50 °C.

The breaker measures 110 mm deep, 138 mm wide, and 248 mm tall.

The part is designed for line protection with no communication function, no voltage trigger, and no trip indicator. As a SENTRON series MCCB, it carries the usual Siemens compliance documentation (UL, IEC, RoHS, REACH) — confirm specific certs with the order code at quote time.

Frequently asked questions

How do I get current pricing and availability for 3VA2325-6HL32-0AC0?

Submit an RFQ through this listing. The part is sourced to order through independent distribution; availability and current pricing are confirmed at quote time.

What is 3VA2325-6HL32-0AC0's listed depth?

The depth is 110 mm (4.33 inches).

What is 3VA2325-6HL32-0AC0's listed width?

The width is 138 mm (5.43 inches).

What compliance documentation does this brand provide for 3VA2325-6HL32-0AC0?

As a Siemens SENTRON MCCB, it typically carries UL, IEC, RoHS, and REACH documentation. Confirm specific certs with the order code at quote time.

MPN
3VA2325-6HL32-0AC0