Skip to main content
Siemens 3VA2325-6HL32-0AJ0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2325-6HL32-0AJ0 MCCB, 250 A, 242 kA at 24

MPN3VA2325-6HL32-0AJ0

Siemens SENTRON molded case circuit breaker, 3VA2325-6HL32-0AJ0, 3-pole, 250 A continuous, 242 kA breaking capacity at 240 V AC, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2325-6HL32-0AJ0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2325-6HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB11

Ratings

3VA2325-6HL32-0AJ0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C250 A
Current at 60 °C250 A
Current at 65 °C250 A
Current at 70 °C250 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.37.5 W

Protection & Trip Unit

3VA2325-6HL32-0AJ0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2325-6HL32-0AJ0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2325-6HL32-0AJ0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2325-6HL32-0AJ0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2325-6HL32-0AJ0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

The Siemens SENTRON 3VA2325-6HL32-0AJ0 is a 3-pole molded case circuit breaker (MCCB) rated for 250 A continuous current across its full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. Breaking capacity runs 242 kA at 240 V AC, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 7.5 kA at 690 V. That spread tells you this breaker is built for high-fault industrial distribution where the available short-circuit current is substantial at lower voltages.

What the ratings mean for fit

The 250 A rating holds flat from 40 °C to 70 °C ambient, so you don't have to oversize for a warm panel. Power loss is 37.5 W maximum — relevant for enclosure thermal calculations when grouping several breakers. The breaker carries a trip indicator and comes with 2 auxiliary switches plus 1 trip alarm switch (HP design), which simplifies status feedback to a PLC or annunciator without adding separate contact blocks.

Panel integration

Dimensions are 248 mm high, 138 mm wide, 110 mm deep. Mounts on a standard DIN rail or with screw-mount lugs. The 3-pole footprint fits a typical MCCB slot in a distribution panel; the 110 mm depth leaves clearance behind a 200 mm deep enclosure door.

Frequently asked questions

Where can I buy 3VA2325-6HL32-0AJ0 and how is it quoted?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA2325-6HL32-0AJ0 at 415 V?

187 kA at 415 V AC, same as at 440 V. At 500 V it drops to 121 kA, and at 690 V to 7.5 kA.

Does 3VA2325-6HL32-0AJ0 require derating at high ambient temperatures?

No — the 250 A rating holds from 40 °C through 70 °C ambient without derating.

MPN
3VA2325-6HL32-0AJ0