Skip to main content
Siemens 3VA2325-6HL32-0CC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2325-6HL32-0CC0 SENTRON MCCB, 250 A, 242 kA at 24

MPN3VA2325-6HL32-0CC0

Siemens SENTRON 3VA2 series, 3-pole molded case circuit breaker, 250 A rated continuous current Iu, 242 kA breaking capacity at 240 V, line protection version with ETU320 electronic trip unit, undervoltage release.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2325-6HL32-0CC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2325-6HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2325-6HL32-0CC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C240 A
Current at 60 °C235 A
Current at 65 °C230 A
Current at 70 °C225 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V40 kA
Power loss, max.40 W

Protection & Trip Unit

3VA2325-6HL32-0CC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320

Construction & Connection

3VA2325-6HL32-0CC0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2325-6HL32-0CC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2325-6HL32-0CC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2325-6HL32-0CC0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

Siemens 3VA2325-6HL32-0CC0 — 250 A MCCB with 242 kA interrupting rating

This SENTRON 3VA2325-6HL32-0CC0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current Iu of 250 A across the 40 °C to 50 °C band before derating begins at 55 °C. The ETU320 electronic trip unit provides adjustable overload and short-circuit protection curves. Breaking capacity hits 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 40 kA at 690 V — enough to handle high-fault utility feeds and transformer secondaries without cascading upstream.

Breaking capacity and selectivity planning

The 242 kA at 240 V and 187 kA at 415 V mean this breaker can sit at the main incoming position in a panel fed by a large transformer — a typical 2000 kVA transformer at 415 V can deliver around 140 kA prospective fault current, so this unit clears that with headroom. At 690 V the 40 kA rating still covers most industrial 690 V distribution. For selectivity coordination downstream, the ETU320 supports I²t-on and I²t-off modes to tune short-time delay against downstream 3VA breakers.

Thermal derating and enclosure fit

Rated 250 A at 40 °C, 45 °C, and 50 °C without derating. At 55 °C it drops to 240 A, at 60 °C to 235 A, at 65 °C to 230 A, and at 70 °C to 225 A. If this breaker lives in a non-ventilated enclosure or a high-ambient switchroom, size the busbars and cable for the derated value at the actual enclosure internal temperature. The maximum power loss is 40 W — that heat must be managed inside the panel. Dimensions: 248 mm high, 138 mm wide, 110 mm deep. The 138 mm width occupies three standard 45 mm pole positions on a DIN rail or mounting plate.

Auxiliary and undervoltage release configuration

Factory-fitted with an undervoltage release (UVR) — design of the auxiliary release is undervoltage release type, so the breaker trips when control voltage drops below the dropout threshold. Two auxiliary switches HQ are included for status feedback to a PLC or DCS. The integrated auxiliary trip module is order code 3VA9608-0BB24. The base switch without auxiliaries is 3VA2325-6HL32-0AA0. No communication function, no phase failure detection, no ground fault monitoring — this is a plain line-protection breaker, not a power meter.

Frequently asked questions

What is the breaking capacity of this MCCB at 415 V?

187 kA at 415 V and at 440 V, dropping to 121 kA at 500 V and 40 kA at 690 V. At 240 V the rating is 242 kA.

Does 3VA2325-6HL32-0CC0 include an undervoltage release?

Yes, the auxiliary release is an undervoltage release (UVR) fitted as standard. Two auxiliary switches HQ are also included.

Where can I buy 3VA2325-6HL32-0CC0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

Will 3VA2325-6HL32-0CC0 fit in a panel designed for a 3VA1112-5EF32-0CA0?

The 3VA2 frame size is physically larger than the 3VA1 — the 3VA2325-6HL32-0CC0 is 138 mm wide versus the 3VA1's narrower footprint, so it will not drop into the same mounting cutout or DIN-rail position without panel modification. The functional difference is also significant: this is a 250 A line-protection breaker with an ETU320 trip unit, while the 3VA1 is a smaller-frame device.

MPN
3VA2325-6HL32-0CC0