Specifications

Identification

3VA2325-6HL32-0DL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2325-6HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22

Ratings

3VA2325-6HL32-0DL0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C250 A
Current at 60 °C250 A
Current at 65 °C250 A
Current at 70 °C250 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.40 W

Protection & Trip Unit

3VA2325-6HL32-0DL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2325-6HL32-0DL0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2325-6HL32-0DL0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2325-6HL32-0DL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2325-6HL32-0DL0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

What this MCCB delivers for your panel

The Siemens 3VA2325-6HL32-0DL0 is a SENTRON molded case circuit breaker sized for 250 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. Its 3-pole design handles line protection duty, with a breaking capacity of 242 kA at 240 V and 187 kA at 415 V, which gives substantial SCCR headroom for most industrial distribution panels. The unit includes an undervoltage release (UVR) and a full auxiliary switch complement: two auxiliary switches, one trip alarm switch, and one electrical alarm switch (HQ configuration).

Breaking capacity across voltage — what it means for coordination

At 240 V the breaker clears 242 kA; at 415 V and 440 V it holds at 187 kA; at 500 V it still manages 121 kA. Only at 690 V does the rating drop to 7.5 kA — a steep roll-off that matters if your panel feeds a 690 V bus. For typical 400 V class distribution the 187 kA figure is well above what most upstream transformers can deliver, so selectivity with downstream devices is straightforward.

Panel fit and dimensions

The breaker measures 138 mm wide, 248 mm high, and 110 mm deep. Those dimensions are standard for a 250 A frame SENTRON 3VA2 MCCB — it mounts on a DIN rail or directly to a backplate with the supplied hardware. The depth of 110 mm means it clears most standard enclosure gland plates without interference.

Frequently asked questions

How do I get pricing and availability for 3VA2325-6HL32-0DL0?

Submit an RFQ through this listing. The part is sourced to order through independent distribution; current pricing and lead time are confirmed at quote time.

What are the key ratings for 3VA2325-6HL32-0DL0?

Continuous current rating is 250 A (no derating from 40 °C to 70 °C). Breaking capacity is 242 kA at 240 V, 187 kA at 415 V, and 7.5 kA at 690 V. It is a 3-pole line-protection MCCB with undervoltage release and a full auxiliary switch set.

Does 3VA2325-6HL32-0DL0 include ground-fault monitoring?

No, this variant is specified without ground-fault monitoring. It is a line-protection-only breaker.

MPN