Siemens SENTRON 3VA2325-6HL32-0JL0 MCCB, 250 A, 3-Pole, 242

MPN3VA2325-6HL32-0JL0

Siemens SENTRON 3VA series, molded case circuit breaker, 3VA2325-6HL32-0JL0, 250 A continuous, 3-pole, 242 kA at 240 V, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2325-6HL32-0JL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2325-6HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22

Ratings

3VA2325-6HL32-0JL0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C250 A
Current at 60 °C250 A
Current at 65 °C250 A
Current at 70 °C250 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.37.5 W

Protection & Trip Unit

3VA2325-6HL32-0JL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2325-6HL32-0JL0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2325-6HL32-0JL0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2325-6HL32-0JL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2325-6HL32-0JL0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

The Siemens SENTRON 3VA2325-6HL32-0JL0 is a 3-pole molded case circuit breaker rated for 250 A continuous current across the full 40 °C to 70 °C ambient range — no derating needed up to that ceiling. Breaking capacity hits 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 7.5 kA at 690 V, so it handles high-fault utility feeds and transformer secondaries without cascading upstream. Designed for line protection, it ships with a shunt trip (STL) auxiliary release and a 2+1+1 auxiliary/trip/alarm switch configuration. The basic switch variant underneath is 3VA2325-6HL32-0AA0.

Breaking capacity and thermal performance

The 250 A frame holds its full rating from 40 °C through 70 °C ambient — no thermal knock-down curve to track. That matters for panels packed into hot enclosures or near process heat. The 242 kA at 240 V is the headline interrupt rating; at 690 V it drops to 7.5 kA, which still covers most 690 V motor branch circuits. The 3-pole construction with shunt trip (STL) means it can be remotely tripped via a control signal, useful for emergency-stop integration or supervisory shutdown.

Panel integration

Dimensions are 248 mm high, 138 mm wide, 110 mm deep — fits standard MCCB panel cutouts and bus-bar spacing for a 250 A frame. No communication module on board; this is a standalone line-protection breaker with voltage-trigger capability and a trip indicator. Storage range is -40 °C to 80 °C; operating range -25 °C to 70 °C. Maximum power loss is 37.5 W — factor into enclosure thermal calculations.

Frequently asked questions

Where can I buy 3VA2325-6HL32-0JL0?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA2325-6HL32-0JL0 at 415 V?

187 kA at 415 V, matching the rating at 440 V.

Does 3VA2325-6HL32-0JL0 include a shunt trip?

Yes, it ships with a shunt trip (STL) auxiliary release plus 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch.

MPN
3VA2325-6HL32-0JL0