The Siemens SENTRON 3VA2325-6HL32-0KL0 is a 3-pole molded case circuit breaker (MCCB) rated for 250 A continuous current across the full operating temperature range from -25 °C to 70 °C — no derating needed up to 70 °C ambient. Breaking capacity hits 242 kA at 240 V and 187 kA at 415/440 V, dropping to 7.5 kA at 690 V. That 242 kA figure at 240 V means it handles fault currents from large transformers or utility feeds without cascading upstream. Designed for line protection, not motor or generator protection.
Dimensions are 248 mm high, 138 mm wide, 110 mm deep — fits standard SENTRON 3VA panel cutouts. The auxiliary switch block includes 2 auxiliary switches plus 1 trip alarm and 1 electrical alarm switch (HQ type), and a shunt trip (STL) release is integrated. No undervoltage release, no ground-fault monitoring, no communication module on this variant. The basic switch is order code 3VA2325-6HL32-0AA0 if you need the bare breaker without accessories.