Skip to main content
Siemens 3VA2325-6HM32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2325-6HM32-0AA0 SENTRON MCCB, 250 A, 3-Pole, ETU3

MPN3VA2325-6HM32-0AA0
Active

Siemens SENTRON 3VA2 series, molded case circuit breaker (MCCB), 3VA2325-6HM32-0AA0, 3-pole, 250 A rated, ETU330 electronic trip unit, line protection version.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2325-6HM32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2325-6HM32-0AA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C242.5 A
Current at 60 °C237.5 A
Current at 65 °C230 A
Current at 70 °C220 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V85 kA
Breaking capacity at 500 V55 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.37.5 W
3VA2325-6HM32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU330
3VA2325-6HM32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2325-6HM32-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2325-6HM32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-40 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2325-6HM32-0AA0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.8 in
Width (in)5.4 in
Depth (in)4.3 in

Product details

The Siemens 3VA2325-6HM32-0AA0 is a SENTRON 3VA2 molded case circuit breaker (MCCB) in a line-protection configuration, rated for 250 A continuous current (Iu) at 40 °C through 50 °C ambient, with an ETU330 electronic trip unit. It is a 3-pole device with a rated insulation voltage (Ui) of 800 V, meaning it can be applied in 480/277 V and 600 V distribution panels without derating for voltage. The breaking capacity is 242 kA at 240 V, 187 kA at 415 V, 85 kA at 440 V, 55 kA at 500 V, and 7.5 kA at 690 V — so at typical 480 V distribution levels you have high fault-current headroom, but at 690 V the interrupting rating drops sharply, which matters if this breaker is applied in a 690 V drive input circuit.

In a sealed panel with limited convection, that 70 °C derate figure is the one to design to if the breaker sits near other heat sources. Dimensions are 248 mm high, 138 mm wide, 110 mm deep (–) — a 3-pole frame that fits standard Siemens 3VA2 mounting patterns. Maximum power loss is 37.5 W, which adds to the panel thermal budget.

Frequently asked questions

Where can I buy 3VA2325-6HM32-0AA0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the breaking capacity of this MCCB at 480 V?

At 440 V it is rated 85 kA, and at 500 V it is 55 kA. For a 480 V system, the value falls between those two — expect roughly 70 kA interpolated, but use the 440 V figure (85 kA) as a conservative bound for 480 V applications unless a specific 480 V rating is confirmed.

What trip unit does 3VA2325-6HM32-0AA0 use?

It uses the ETU330 electronic overcurrent release, which provides adjustable long-time pickup and delay (tr min 0.5 s, tr max 17 s) and is designed for line protection — not motor or generator protection.

MPN
3VA2325-6HM32-0AA0