The 3-pole form factor leaves room for side-mounted accessories. Undervoltage release (UVR) is built in — verify coil voltage matches your control circuit before wiring.
Thermal derating and endurance
Rated current holds at 250 A from 40 °C up to 50 °C, then steps down to 240 A at 55 °C, 235 A at 60 °C, 230 A at 65 °C, and 225 A at 70 °C (–). Mechanical endurance is 15,000 operations. Maximum power loss is 40 W — factor that into enclosure ventilation.