Skip to main content
Siemens 3VA2325-6HN32-0BC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2325-6HN32-0BC0 SENTRON MCCB, 250 A, 3-Pole, 242

MPN3VA2325-6HN32-0BC0

Siemens SENTRON 3VA2325-6HN32-0BC0, molded case circuit breaker, 250 A continuous, 3-pole, 242 kA interrupting at 240 V, line protection design, undervoltage release, 2 auxiliary switches HQ.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2325-6HN32-0BC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2325-6HN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2325-6HN32-0BC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C250 A
Current at 60 °C250 A
Current at 65 °C250 A
Current at 70 °C250 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.40 W
3VA2325-6HN32-0BC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2325-6HN32-0BC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2325-6HN32-0BC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2325-6HN32-0BC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2325-6HN32-0BC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

The Siemens 3VA2325-6HN32-0BC0 is a SENTRON molded case circuit breaker rated for 250 A continuous at 40 °C through 70 °C — no derating needed across that span, which simplifies panel thermal budgeting. Its 3-pole line-protection design carries a 242 kA interrupting capacity at 240 V, dropping to 187 kA at 415/440 V, 121 kA at 500 V, and 7.5 kA at 690 V, so it handles high-fault utility feeds and transformer secondaries without cascading upstream.

The breaker measures 248 mm high, 138 mm wide, and 110 mm deep — a standard SENTRON 3VA footprint that fits existing panel cutouts and DIN-rail adapters. Maximum power loss is 40 W, so ventilation in a sealed enclosure should account for that dissipation. Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C.

Frequently asked questions

What are the interrupting ratings for 3VA2325-6HN32-0BC0 at different voltages?

242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 7.5 kA at 690 V.

What is the continuous current rating of this MCCB?

250 A continuous from 40 °C through 70 °C ambient — no derating required across that range.

Where can I buy 3VA2325-6HN32-0BC0 and how is it quoted?

Sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
3VA2325-6HN32-0BC0