Skip to main content
Siemens 3VA2325-6HN32-0JC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2325-6HN32-0JC0 SENTRON MCCB, 250 A, 3-Pole, 242

MPN3VA2325-6HN32-0JC0

Siemens SENTRON, Molded case circuit breaker, 3VA2325-6HN32-0JC0, 250 A, 3-pole, 242 kA at 240 V, line protection with shunt trip.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2325-6HN32-0JC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2325-6HN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2325-6HN32-0JC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C250 A
Current at 60 °C250 A
Current at 65 °C250 A
Current at 70 °C250 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.37.5 W

Protection & Trip Unit

3VA2325-6HN32-0JC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2325-6HN32-0JC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2325-6HN32-0JC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2325-6HN32-0JC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2325-6HN32-0JC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

What the ratings mean for your panel

The Siemens SENTRON 3VA2325-6HN32-0JC0 is a 3-pole molded case circuit breaker rated for 250 A continuous current across the full 40–70 °C ambient range — no derating needed as the panel warms up. Its interrupting capacity is voltage-dependent: 242 kA at 240 V, 187 kA at 415/440 V, 121 kA at 500 V, and 7.5 kA at 690 V. That 242 kA figure at 240 V means it handles the full fault current available at a large service entrance without cascading upstream — critical for selectivity in a main or feeder breaker position. The 7.5 kA at 690 V still covers most industrial motor branch circuits.

Line protection with integrated shunt trip

This MCCB is designed for line protection (cable/feeder) rather than motor or generator protection — the trip curve and accessories are tuned for overcurrent on distribution circuits. It ships with a shunt trip (STL) auxiliary release and two HQ auxiliary switches, so you can remotely trip the breaker or signal its status back to a PLC without adding an external undervoltage release module. The basic switch core is order code 3VA2325-6HN32-0AA0.

Physical fit and panel integration

Dimensions are 110 mm deep × 138 mm wide × 248 mm high. The 138 mm width is standard for a 3-pole MCCB in this frame size — it fits the usual DIN-rail or panel-mount footprint without surprises. Maximum power loss is 37.5 W, so account for that heat in a sealed enclosure. Operating temperature range is -25 to 70 °C; storage range is -40 to 80 °C.

Frequently asked questions

Where can I buy 3VA2325-6HN32-0JC0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the interrupting capacity of 3VA2325-6HN32-0JC0 at different voltages?

242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 7.5 kA at 690 V. The rating drops with voltage, so verify the available fault current at your system voltage.

Does 3VA2325-6HN32-0JC0 include a shunt trip?

Yes, it comes with a shunt trip (STL) auxiliary release and two HQ auxiliary switches for remote tripping and status feedback.

MPN
3VA2325-6HN32-0JC0