Skip to main content
Siemens 3VA2325-7JQ42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2325-7JQ42-0AA0 SENTRON MCCB, 250 A, 4-Pole, ETU5

MPN3VA2325-7JQ42-0AA0
Active

Siemens SENTRON 3VA2, molded case circuit breaker, 250 A, 4-pole, ETU560 electronic trip, 330 kA at 240 V, line protection.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2325-7JQ42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA2325-7JQ42-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C250 A
Current at 60 °C250 A
Current at 65 °C250 A
Current at 70 °C250 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.37.5 W

Protection & Trip Unit

3VA2325-7JQ42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L + N conductor

Construction & Connection

3VA2325-7JQ42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2325-7JQ42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2325-7JQ42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2325-7JQ42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width184 mm
Depth110 mm
Height (in)9.76 in
Width (in)7.24 in
Depth (in)4.33 in

Product details

What this MCCB delivers

The Siemens 3VA2325-7JQ42-0AA0 is a SENTRON 3VA2 molded case circuit breaker rated for 250 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. Four poles, line-protection version, fitted with the ETU560 electronic trip unit. The interrupting capacity is 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 7.5 kA at 690 V. That 330 kA figure at 240 V is the number that governs selectivity in high-fault utility or transformer-secondaries; the 690 V rating of 7.5 kA is the practical ceiling for this frame in IEC applications.

Trip unit and protection profile

The ETU560 is an electronic trip unit with adjustable long-time, short-time, instantaneous, and ground-fault protection. The ground-fault monitoring uses summation current formation on the L+N conductor, which means it detects residual current without a separate sensor core — useful in retrofit panels where space for a toroid is tight. Rated insulation voltage is 800 V. Maximum power loss is 37.5 W, which factors into enclosure thermal calculations if the breaker is enclosed.

Panel fit and environment

Dimensions are 248 mm high, 184 mm wide, 110 mm deep. The front face carries an IP40 protection class — suitable for general indoor panel environments but not washdown. Operating temperature range is -25 °C to 70 °C; storage from -40 °C to 80 °C. Communication function is built in, and a motor drive option is available for remote switching. The 4-pole format with line protection means it switches all three phases plus neutral, with the neutral pole typically switched but not protected — confirm the neutral protection scheme per your local code.

Frequently asked questions

What is the interrupting capacity of 3VA2325-7JQ42-0AA0 at 240 V?

330 kA at 240 V. At 415 V and 440 V it is 242 kA, at 500 V it is 187 kA, and at 690 V it is 7.5 kA.

Where can I buy 3VA2325-7JQ42-0AA0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the continuous current rating of 3VA2325-7JQ42-0AA0?

250 A continuous, with no derating required from 40 °C up to 70 °C ambient.

What trip unit does 3VA2325-7JQ42-0AA0 use?

The ETU560 electronic trip unit with adjustable long-time, short-time, instantaneous, and ground-fault protection. Ground-fault detection uses summation current on the L+N conductor.