Skip to main content
Siemens 3VA2325-7MN32-0AJ0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2325-7MN32-0AJ0 MCCB, 250 A, 330 kA at 24

MPN3VA2325-7MN32-0AJ0

Siemens SENTRON 3VA2325-7MN32-0AJ0, molded case circuit breaker, 3-pole, 250 A, 330 kA at 240 V, ETU350M electronic trip unit, 2 aux + 1 alarm switch.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2325-7MN32-0AJ0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionMotor protection
Basic switch (supplied) ref.3VA2325-7MN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB11

Ratings

3VA2325-7MN32-0AJ0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C240 A
Current at 60 °C235 A
Current at 65 °C230 A
Current at 70 °C225 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.37.5 W

Protection & Trip Unit

3VA2325-7MN32-0AJ0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M

Construction & Connection

3VA2325-7MN32-0AJ0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2325-7MN32-0AJ0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2325-7MN32-0AJ0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2325-7MN32-0AJ0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

What this MCCB delivers

The Siemens SENTRON 3VA2325-7MN32-0AJ0 is a 3-pole molded case circuit breaker rated for 250 A continuous current, with a breaking capacity of 330 kA at 240 V AC — enough to handle high-fault utility feeds or transformer secondaries without cascading upstream. The ETU350M electronic trip unit provides adjustable overload and short-circuit protection, plus phase failure detection, so it suits motor protection duty in a distribution panel.

Breaking capacity across voltages

At 415 V and 440 V the breaker still delivers 242 kA; at 500 V it holds 187 kA; at 690 V it drops to 52.5 kA. That voltage-dependent curve means you can use this same frame for 480 V or 600 V class panels as long as the available fault current stays under the respective rating.

Temperature derating — what the 250 A rating really means

The breaker carries its full 250 A from 40 °C up to 50 °C. At 55 °C it derates to 240 A, at 60 °C to 235 A, at 65 °C to 230 A, and at 70 °C to 225 A. If your panel ambient runs hot — say, next to a drive cabinet or in a non-conditioned enclosure — size the load side for the derated figure, not the nameplate.

Auxiliary contacts and trip indication

Factory-fitted with 2 auxiliary switches plus 1 trip alarm switch (HP type). The trip indicator is mechanical — visible through the front window — so a quick walk-by confirms the breaker state without opening the door.

Frequently asked questions

What is the breaking capacity of 3VA2325-7MN32-0AJ0 at 240 V?

330 kA at 240 V AC, with 242 kA at 415 V and 440 V, 187 kA at 500 V, and 52.5 kA at 690 V.

What trip unit does this MCCB use?

The ETU350M electronic trip unit with adjustable overload and short-circuit protection, plus phase failure detection.

Where can I buy 3VA2325-7MN32-0AJ0?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quote.

MPN
3VA2325-7MN32-0AJ0