Skip to main content
Siemens 3VA2325-7MN32-0BL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2325-7MN32-0BL0 SENTRON MCCB, 250 A, 330 kA at 24

MPN3VA2325-7MN32-0BL0

Siemens SENTRON 3VA2 molded case circuit breaker, 3VA2325-7MN32-0BL0, 250 A rated continuous current, 3-pole, motor protection version, ETU350M electronic trip unit, 330 kA interrupting capacity at 240 V AC.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2325-7MN32-0BL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionMotor protection
Basic switch (supplied) ref.3VA2325-7MN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22

Ratings

3VA2325-7MN32-0BL0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C240 A
Current at 60 °C235 A
Current at 65 °C230 A
Current at 70 °C225 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.40 W

Protection & Trip Unit

3VA2325-7MN32-0BL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M

Construction & Connection

3VA2325-7MN32-0BL0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2325-7MN32-0BL0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2325-7MN32-0BL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2325-7MN32-0BL0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

What this MCCB delivers in the panel

The Siemens 3VA2325-7MN32-0BL0 is a SENTRON molded case circuit breaker (MCCB) rated for a continuous current Iu of 250 A, with an interrupting capacity that hits 330 kA at 240 V AC and still holds 242 kA at 415 V and 440 V. That SCCR headroom means it can sit upstream of a high-fault panel without needing a current-limiting fuse ahead of it — the breaker itself clears the fault. The ETU350M electronic trip unit gives you adjustable long-time, short-time, and instantaneous protection curves, plus phase-failure detection built in. Undervoltage release (UVR) is integrated, so a loss of control voltage drops the breaker open — useful for emergency-stop chains or safety circuits that need a guaranteed disconnect on power loss. Thermal derating is published across the full operating range: it carries the full 250 A up to 50 °C ambient, then steps down to 240 A at 55 °C, 235 A at 60 °C, 230 A at 65 °C, and 225 A at 70 °C. If your panel runs hot — say, a packed enclosure near a furnace line — that curve tells you exactly how much margin you lose. The auxiliary contact block ships with 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch (HQ configuration), giving you four separate signal paths for status feedback to a PLC or annunciator panel.

Dimensions and panel fit

The 3VA2 frame measures 248 mm high, 138 mm wide, and 110 mm deep. That depth includes the arc chamber and the rear terminal space — important when sizing the enclosure depth, especially if you're back-paneling with busbars or a cable duct behind the breaker. The 3-pole footprint matches the standard SENTRON 3VA2 cutout, so a panel originally laid out for a 3VA2 MCCB accepts this unit without re-drilling or re-bussing.

Key ratings at a glance

Rated insulation voltage Ui is 800 V, so it's rated for 690 V systems with margin. Maximum power loss is 40 W — worth noting for thermal calculations in a sealed enclosure. Latching endurance is 15 000 operations, which is typical for a motor-protection MCCB that sees occasional switching, not daily cycling. Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C.

Frequently asked questions

Where can I buy 3VA2325-7MN32-0BL0 and what is the lead time?

This part is sourced and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time through our independent distribution network.

What is the interrupting capacity at 415 V?

At 415 V AC the interrupting capacity is 242 kA. At 240 V it is 330 kA, and at 690 V it drops to 52.5 kA.

What trip unit does this MCCB use?

It uses the ETU350M electronic trip unit, with adjustable long-time, short-time, and instantaneous protection, plus phase failure detection.

Does it include an undervoltage release?

Yes, an undervoltage release (UVR) is integrated — the breaker opens on loss of control voltage.

MPN