Skip to main content
Siemens 3VA2325-7MN32-0HA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2325-7MN32-0HA0 SENTRON MCCB, 250A, 330kA at 240V

MPN3VA2325-7MN32-0HA0

Siemens SENTRON 3VA2325-7MN32-0HA0, molded case circuit breaker, motor protection version, 3-pole, 250 A, breaking capacity 330 kA at 240 V AC, with ETU350M trip unit and shunt trip release.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2325-7MN32-0HA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionMotor protection
Basic switch (supplied) ref.3VA2325-7MN32-0AA0

Ratings

3VA2325-7MN32-0HA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C240 A
Current at 60 °C235 A
Current at 65 °C230 A
Current at 70 °C225 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.37.5 W

Protection & Trip Unit

3VA2325-7MN32-0HA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M

Construction & Connection

3VA2325-7MN32-0HA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2325-7MN32-0HA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2325-7MN32-0HA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2325-7MN32-0HA0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

Motor protection MCCB with 250 A continuous rating and 330 kA interrupting capacity

The Siemens SENTRON 3VA2325-7MN32-0HA0 is a 3-pole molded case circuit breaker (MCCB) in the motor protection version, rated for a continuous current Iu of 250 A. Its breaking capacity reaches 330 kA at 240 V AC, 242 kA at 415/440 V, 187 kA at 500 V, and 52.5 kA at 690 V — figures that place it in the high-interrupting class for industrial feeder and motor branch circuits. The rated insulation voltage Ui is 800 V. This version ships with an ETU350M electronic trip unit (overcurrent release) and an integrated shunt trip (STL) auxiliary release. It includes phase failure detection and a voltage trigger, but no undervoltage release, no auxiliary contacts, no ground fault monitoring, and no communication function. The basic switch is order code 3VA2325-7MN32-0AA0; the integrated auxiliary trip is 3VA9688-0BL30. Rated current holds at 250 A from 40 °C through 50 °C, then derates to 240 A at 55 °C, 235 A at 60 °C, 230 A at 65 °C, and 225 A at 70 °C. Mechanical endurance is 15,000 cycles. Maximum power loss is 37.5 W. Operating temperature range is -25 °C to +70 °C; storage range is -40 °C to +80 °C.

Panel fit and mounting dimensions

The 3VA2325-7MN32-0HA0 measures 248 mm high × 138 mm wide × 110 mm deep. It mounts on a DIN rail or directly to a backplate via the SENTRON 3VA series mounting accessories. The 138 mm width is three pole spaces at 46 mm per pole — standard for this class of MCCB. Verify gland plate clearance for the 110 mm depth plus wiring bend radius when laying out the enclosure.

Frequently asked questions

Where can I buy 3VA2325-7MN32-0HA0 and get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm current availability and pricing — no stock or price figures are published here.

What is the breaking capacity of 3VA2325-7MN32-0HA0 at 240 V?

330 kA at 240 V AC. At 415 V and 440 V it is 242 kA, at 500 V it is 187 kA, and at 690 V it is 52.5 kA.

What trip unit does the 3VA2325-7MN32-0HA0 use?

It uses the ETU350M electronic overcurrent release with a shunt trip (STL) auxiliary release. It includes phase failure detection but no ground fault monitoring, no undervoltage release, and no communication function.

MPN
3VA2325-7MN32-0HA0