Specifications

3VA2340-0HN42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2340-0HN42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C385 A
Current at 60 °C370 A
Current at 65 °C355 A
Current at 70 °C340 A
Switching capacity classE
Breaking capacity at 415 V440 kA
Breaking capacity at 690 V187 kA
Power loss, max.96 W
3VA2340-0HN42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
3VA2340-0HN42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2340-0HN42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2340-0HN42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2340-0HN42-0AA0 — Mechanical
ParameterValue
Height248 mm
Width184 mm
Depth110 mm
Height (in)9.76 in
Width (in)7.24 in
Depth (in)4.33 in

Product details

The Siemens SENTRON 3VA2340-0HN42-0AA0 is a 4-pole molded case circuit breaker (MCCB) rated for 400 A continuous current at 40 °C, with an electronic overcurrent release type ETU350.

The 400 A rating holds across 40 °C to 50 °C without derating; at 55 °C it derates to 385 A, at 60 °C to 370 A, and at 70 °C to 340 A. If your enclosure ambient runs above 50 °C, factor the thermal curve into the load schedule. The IP40 front protection is typical for enclosed distribution; no additional gasketing is needed inside a rated enclosure. The ETU350 electronic trip unit offers adjustable N-conductor protection (OFF, 50%, 100%) and a fixed I²t curve — no adjustable I-t setting. The undervoltage release and voltage trigger are not fitted on this variant; communication function is absent, so it is a standalone thermal-magnetic replacement with electronic trip logic.

Frequently asked questions

How do I get current pricing and availability for 3VA2340-0HN42-0AA0?

Submit an RFQ through this listing; availability and current pricing are confirmed at quote time through independent distribution channels.

What is 3VA2340-0HN42-0AA0's interrupting rating?

It is rated 440 kA at 415 V AC and 187 kA at 690 V AC.

What trip unit does 3VA2340-0HN42-0AA0 use?

It uses the ETU350 electronic overcurrent release with adjustable N-conductor protection (OFF, 50%, 100%).

MPN