Skip to main content
Siemens 3VA2340-0KP42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-0KP42-0AA0 MCCB, 200 kA @ 415 V, 400 A

MPN3VA2340-0KP42-0AA0
Active

Siemens 3VA2 IEC frame 400, 200 kA @ 415 V, 4-pole, line protection ETU850 LSI, In=400 A, overload Ir=160-400 A, short-circuit Isd=0.6-10xIn, Ii=1.5-12xIn, neutral protection adjustable.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2340-0KP42-0AA0 — Specifications
ParameterValue
Group codeP360
Product group5374
Product classC: products manufactured / produced to order, which cannot be reused or re-utilized or be returned against credit.
Series3VA Molded Case Circuit Breakers up to 1600 A, IEC
Export control regulationsAL : N / ECCN : 9N9999
Compliance with the substance restrictions according to RoHS directiveSince: 01-10-19

Product details

400 A frame with 200 kA interrupting capacity

The Siemens 3VA2340-0KP42-0AA0 is a 4-pole IEC molded case circuit breaker in the 3VA2 family, built on a 400 A frame with an interrupting capacity of 200 kA at 415 V (breaking capacity class E).

ETU850 LSI protection profile

Fitted with an ETU850 electronic trip unit configured for LSI protection: long-time pickup Ir adjustable 160 A to 400 A, short-time pickup Isd 0.6 to 10× In, and instantaneous pickup Ii 1.5 to 12× In. Neutral conductor protection is adjustable (OFF, up to 100%). This makes it suitable for selective coordination downstream of a main breaker — the adjustable time delays let you stage tripping so a feeder fault clears before the main trips.

Compliance and substance declarations

RoHS compliant since 01-10-19. Export control classification: AL N / ECCN 9N9999. No UL or CSA listing appears in the record — this is an IEC-rated device for markets following IEC 60947-2.

Packaging and handling

Packaged singly (packaging quantity 1). Shipping dimensions 265 × 165 × 170 mm. The 400 A frame size is substantial — expect panel cutout and bus bar planning accordingly, not a DIN-rail clip-in.

Frequently asked questions

Where can I buy 3VA2340-0KP42-0AA0 and how do I get a price?

This part is sourced and quoted to order through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time, as the made-to-order status means no shelf stock.

What is the breaking capacity of 3VA2340-0KP42-0AA0?

Breaking capacity class E: Icu = 200 kA at 415 V. This is the maximum short-circuit current the breaker can safely interrupt at that voltage level.

What compliance documentation does this breaker carry?

RoHS compliant since 01-10-19. REACH Article 33 duty to inform applies due to lead content above 0.1% w/w. Export control classification AL N / ECCN 9N9999. This is an IEC-rated device per IEC 60947-2.

MPN
3VA2340-0KP42-0AA0