Breaking capacity varies with system voltage: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 7.5 kA at 690 V. This gives the breaker substantial fault-current headroom for most low-voltage commercial and industrial mains.
Above that, the continuous current derates linearly: 385 A at 55 °C, 370 A at 60 °C, 355 A at 65 °C, and 340 A at 70 °C.
Mounting dimensions
Panel cutout and mounting pattern follow the standard SENTRON 3VA frame footprint for this current class.