Skip to main content
Siemens 3VA2340-5HL32-0AG0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-5HL32-0AG0 SENTRON MCCB, 400 A, 3-Pole, ETU3

MPN3VA2340-5HL32-0AG0

Siemens SENTRON 3VA2340-5HL32-0AG0, molded case circuit breaker, 3-pole, 400 A, ETU320 electronic trip unit, line protection, 187 kA at 240 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2340-5HL32-0AG0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2340-5HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB11
3VA2340-5HL32-0AG0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C385 A
Current at 60 °C370 A
Current at 65 °C355 A
Current at 70 °C340 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V17 kA
Power loss, max.96 W
3VA2340-5HL32-0AG0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2340-5HL32-0AG0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2340-5HL32-0AG0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2340-5HL32-0AG0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2340-5HL32-0AG0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

The Siemens SENTRON 3VA2340-5HL32-0AG0 is a 3-pole molded case circuit breaker (MCCB) rated for 400 A continuous current (Iu) at 40 °C, with an ETU320 electronic trip unit for line protection. This is the breaker you specify when the main feeder or a large downstream load needs adjustable thermal-magnetic or electronic protection in a 400 A frame — common for industrial distribution panels, machine tool infeed, or building main switchboards. Breaking capacity is voltage-dependent: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V. At 690 V the 17 kA figure is lower but still adequate for most motor-control-center applications where the upstream transformer impedance limits fault current. The ETU320 trip unit provides electronic overcurrent protection with adjustable settings (not detailed in this listing but standard for the ETU320 platform — typically long-time pickup, short-time pickup and delay, instantaneous, and ground fault).

Panel footprint and thermal derating

Depth of 110 mm means it fits within a 200 mm-deep enclosure with room for rear cable connections and the integrated auxiliary trip (supplied as 3VA9608-0BB11). Thermal derating is published: full 400 A from 40 °C through 50 °C, then 385 A at 55 °C, 370 A at 60 °C, 355 A at 65 °C, and 340 A at 70 °C. Maximum power loss is 96 W, which contributes to the enclosure's thermal budget.

The basic switch supplied inside this breaker is order code 3VA2340-5HL32-0AA0, and the integrated auxiliary trip is 3VA9608-0BB11. If you are repairing an existing unit, those subcomponents are orderable separately. The auxiliary contact configuration (1 auxiliary switch + 1 trip alarm switch HP) is fixed at the factory — not field-convertible without replacing the auxiliary contact block.

Frequently asked questions

How do I get current pricing and availability for 3VA2340-5HL32-0AG0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What are the key ratings for this MCCB?

Rated continuous current Iu is 400 A at 40 °C, with breaking capacity of 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V. It is a 3-pole breaker with an ETU320 electronic trip unit for line protection.

What is the panel footprint of this breaker?

Dimensions are 248 mm high, 138 mm wide, and 110 mm deep. The 138 mm width occupies three 45 mm pole spaces on a DIN rail or panel-mount base.

MPN
3VA2340-5HL32-0AG0