Skip to main content
Siemens 3VA2340-5HL32-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-5HL32-0AH0 SENTRON MCCB, 400 A, 3-Pole, ETU3

MPN3VA2340-5HL32-0AH0

Siemens SENTRON 3VA2340-5HL32-0AH0, molded case circuit breaker, 3-pole, 400 A rated continuous current, ETU320 electronic trip unit, line protection version, breaking capacity 187 kA at 240 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2340-5HL32-0AH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2340-5HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA2340-5HL32-0AH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C385 A
Current at 60 °C370 A
Current at 65 °C355 A
Current at 70 °C340 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V17 kA
Power loss, max.96 W
3VA2340-5HL32-0AH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2340-5HL32-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2340-5HL32-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA2340-5HL32-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2340-5HL32-0AH0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

The Siemens SENTRON 3VA2340-5HL32-0AH0 is a 3-pole molded case circuit breaker rated for 400 A continuous current at 40 °C, with an ETU320 electronic trip unit for adjustable overload and short-circuit protection. The 138 mm width and 248 mm height fit standard SENTRON panel cutouts, and the 110 mm depth leaves room behind the door for wiring gutters.

Rated 400 A up to 50 °C ambient; above that it derates to 385 A at 55 °C, 370 A at 60 °C, 355 A at 65 °C, and 340 A at 70 °C. The maximum power loss of 96 W at rated current means the enclosure needs ventilation or a larger cubicle to keep ambient under the trip unit's calibration.

The interrupting ratings step down with system voltage: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V.

Auxiliary contacts and trip signaling

The trip alarm closes only on a fault trip — not on manual switching — so it can drive a remote annunciator or PLC input that distinguishes overload from a maintenance disconnect.

Frequently asked questions

Where can I buy 3VA2340-5HL32-0AH0 and how do I get a price?

Sourced through independent distribution and quoted to order against an RFQ. Submit a request for current pricing and availability; the quote confirms lead time at the time of inquiry.

What is the breaking capacity of this MCCB at 415 V?

121 kA at 415 V, same as at 440 V. At 500 V it drops to 75.6 kA, and at 690 V to 17 kA.

What auxiliary contacts does the 3VA2340-5HL32-0AH0 include?

Two auxiliary switches plus one trip alarm switch (HQ type). The trip alarm activates only on a fault trip, not on manual switching.

MPN
3VA2340-5HL32-0AH0