Skip to main content
Siemens 3VA2340-5HL32-0HA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-5HL32-0HA0 SENTRON MCCB, 400 A, 3-Pole, Line

MPN3VA2340-5HL32-0HA0

Siemens SENTRON 3VA2340-5HL32-0HA0, molded case circuit breaker, 3-pole, 400 A rated continuous current Iu, line protection version with ETU320 overcurrent release, shunt trip (STL), breaking capacity 187 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2340-5HL32-0HA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2340-5HL32-0AA0
3VA2340-5HL32-0HA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C385 A
Current at 60 °C370 A
Current at 65 °C355 A
Current at 70 °C340 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V17 kA
Power loss, max.96 W
3VA2340-5HL32-0HA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2340-5HL32-0HA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2340-5HL32-0HA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2340-5HL32-0HA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2340-5HL32-0HA0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

The Siemens SENTRON 3VA2340-5HL32-0HA0 is a 3-pole molded case circuit breaker (MCCB) rated for 400 A continuous current at 40 °C, with the ETU320 electronic trip unit handling overcurrent protection. It carries a breaking capacity of 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V — figures that tell you this breaker is sized for high-fault industrial distribution, not light commercial. The shunt trip (STL) design allows remote tripping via a voltage trigger, which is useful for emergency-off or interlock circuits.

The 400 A rating holds flat from 40 °C through 50 °C, then steps down: 385 A at 55 °C, 370 A at 60 °C, 355 A at 65 °C, and 340 A at 70 °C.

Frequently asked questions

Where can I buy 3VA2340-5HL32-0HA0 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for current pricing and availability.

What is the breaking capacity of this MCCB at 415 V?

121 kA at 415 V, which matches the rating at 440 V. At 500 V it drops to 75.6 kA, and at 690 V to 17 kA.

What trip unit does the 3VA2340-5HL32-0HA0 use?

The ETU320 electronic overcurrent release. It is a line-protection version with a shunt trip (STL) for remote voltage-triggered tripping.

Does this breaker include auxiliary contacts or ground-fault monitoring?

No. It ships without auxiliary contacts and without ground-fault monitoring. No communication function or phase-failure detection either.

MPN