Skip to main content
Siemens 3VA2340-5HL32-0JC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-5HL32-0JC0 SENTRON MCCB, 400 A, 3-Pole, 187

MPN3VA2340-5HL32-0JC0

Siemens SENTRON 3VA2340-5HL32-0JC0, molded case circuit breaker, 3-pole, 400 A rated continuous current, line protection design, 187 kA interrupting at 240 V, 110 mm depth, 138 mm width, 248 mm height.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2340-5HL32-0JC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2340-5HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2340-5HL32-0JC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C385 A
Current at 60 °C370 A
Current at 65 °C355 A
Current at 70 °C340 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.96 W

Protection & Trip Unit

3VA2340-5HL32-0JC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2340-5HL32-0JC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2340-5HL32-0JC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2340-5HL32-0JC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2340-5HL32-0JC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

What this 3VA2340-5HL32-0JC0 is and what it does

The Siemens 3VA2340-5HL32-0JC0 is a SENTRON molded case circuit breaker (MCCB) rated for 400 A continuous current in a 3-pole configuration, designed for line protection in distribution panels. Its interrupting capacity hits 187 kA at 240 V and 121 kA at 415 V, so it clears high-fault currents without cascading upstream — critical for main or feeder breakers in industrial switchgear. The breaker carries a shunt trip (STL) auxiliary release and two auxiliary switches (HQ design), meaning it can be tripped remotely and signal its status back to a PLC or annunciator.

Breaking capacity and thermal derating — the real selection numbers

The 400 A frame is rated for a minimum trip setting of 600 A and a maximum of 4 000 A, so it covers feeder circuits from moderate to high overload. The interrupting rating drops as voltage climbs: 187 kA at 240 V, 121 kA at both 415 V and 440 V, 75.6 kA at 500 V, and 7.5 kA at 690 V. That 690 V figure is the one to watch if you're on a 690 V distribution — it's still a solid number but well below the low-voltage ratings. Thermal derating is published per degree: the breaker holds 400 A up to 50 °C, then steps down to 385 A at 55 °C, 370 A at 60 °C, 355 A at 65 °C, and 340 A at 70 °C. If your panel ambient runs hot, size the load accordingly.

Panel fit and integration

The breaker measures 248 mm high, 138 mm wide, and 110 mm deep — a standard 3-pole MCCB footprint that fits most distribution panelboards and switchgear cubicles. The 110 mm depth (4.33 in) is shallow enough for compact enclosures. It ships with the basic switch (3VA2340-5HL32-0AA0) and the auxiliary switches are pre-installed; the shunt trip is integrated, so no field wiring of a separate undervoltage release is needed. Power loss is 96 W max at rated load — account for that in your thermal budget if the panel is densely packed.

Frequently asked questions

Where can I buy 3VA2340-5HL32-0JC0 and get a price?

This breaker is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the interrupting capacity of 3VA2340-5HL32-0JC0 at 415 V?

At 415 V, the interrupting rating is 121 kA. The same rating applies at 440 V. At 240 V it's 187 kA, dropping to 75.6 kA at 500 V and 7.5 kA at 690 V.

Does 3VA2340-5HL32-0JC0 include a shunt trip?

Yes, it comes with a shunt trip (STL) auxiliary release and two auxiliary switches (HQ design). No undervoltage release is fitted. The basic switch is order code 3VA2340-5HL32-0AA0.

MPN
3VA2340-5HL32-0JC0