The interrupting ratings are serious: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 7.5 kA at 690 V — so it can handle high-fault utility feeds without cascading upstream.
Thermal derating and sizing
Above that it derates: 385 A at 55 °C, 370 A at 60 °C, 355 A at 65 °C, and 340 A at 70 °C. If your panel runs hot, size the load side accordingly.
It ships without auxiliary switches or undervoltage release; the only auxiliary release is the shunt trip (STL). If you need a UVR or ground-fault module, this variant doesn't carry them.