The 3VA2340-5HL42-0KH0: Breaking capacity drops from 187 kA at 240 V to 121 kA at 415 V and 440 V, then 75.6 kA at 500 V, and 17 kA at 690 V — the high 240 V figure covers low-voltage utility feeds; the 415 V rating is the one to check for most European industrial mains. Thermal derating begins at 55 °C: 385 A at 55 °C, 370 A at 60 °C, 355 A at 65 °C, 340 A at 70 °C. Up to 50 °C you get the full 400 A.
Auxiliary and trip configuration
Shunt trip (STL) installed as standard — designated 3VA9688-0BL33. The basic switch variant is 3VA2340-5HL42-0AA0.
Latching endurance rated at 15 000 cycles. Maximum power loss 96 W at rated load. Rated insulation voltage Ui 800 V. Dimensions: 110 mm deep, 184 mm wide, 248 mm high — fits standard MCCB panel cutouts.
