Skip to main content
Siemens 3VA2340-5HN32-0AB0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2340-5HN32-0AB0 MCCB, 400 A, 3-Pole, 187

MPN3VA2340-5HN32-0AB0

Siemens SENTRON, Molded case circuit breaker, 3VA2340-5HN32-0AB0, 400 A, 3-pole, 187 kA at 240 V, line protection.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2340-5HN32-0AB0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2340-5HN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA11
3VA2340-5HN32-0AB0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C385 A
Current at 60 °C370 A
Current at 65 °C355 A
Current at 70 °C340 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.96 W
3VA2340-5HN32-0AB0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2340-5HN32-0AB0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2340-5HN32-0AB0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2340-5HN32-0AB0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2340-5HN32-0AB0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

At 240 V it interrupts 187 kA, dropping to 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 7.5 kA at 690 V — the full interrupting rating curve you need for selectivity studies. The 400 A frame carries through 50 °C without derating; above that, it steps down to 385 A at 55 °C, 370 A at 60 °C, 355 A at 65 °C, and 340 A at 70 °C.

The 3-pole form factor with 2 HP auxiliary switches mounts directly onto the DIN rail or screw-fixed mounting plate common in industrial enclosures.

Environmental & Compliance — Full Temperature Range, No Undervoltage Release

Frequently asked questions

Where can I buy 3VA2340-5HN32-0AB0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm current availability and pricing.

What is 3VA2340-5HN32-0AB0's listed depth (110 mm) on this component line?

The depth is 110 mm (4.33 in), with a width of 138 mm (5.43 in) and height of 248 mm (9.76 in).

Will 3VA2340-5HN32-0AB0 drop into a panel that was specified around 3VA2225-5HN42-0BB0 without rewiring?

No — the 3VA2225-5HN42-0BB0 is a different frame size and rating. The 3VA2340-5HN32-0AB0 is a 400 A, 3-pole MCCB; verify your panel's busbar spacing, cutout dimensions, and cable terminations before substituting. The 138 mm width and 248 mm height may not match the smaller frame.

What compliance documentation does this brand provide for 3VA2340-5HN32-0AB0 (RoHS, REACH, UL, IEC)?

As a Siemens SENTRON product, this MCCB is designed to meet IEC 60947-2 and UL 489 standards for molded case circuit breakers. RoHS and REACH compliance declarations are standard with the brand's documentation package for this series.

MPN
3VA2340-5HN32-0AB0