Skip to main content
Siemens 3VA2340-5HN32-0DJ0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-5HN32-0DJ0 Circuit Breaker, 55kA @ 415V, 400

MPN3VA2340-5HN32-0DJ0

Siemens 3VA2 IEC frame 400, breaking capacity class M, Icu=55kA @ 415V, 3-pole, line protection ETU350 LSI, In=400A, undervoltage release 208-230 V AC 50/60 Hz, with auxiliary switch and trip alarm.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Product details

Three-pole, line protection via an ETU350 electronic trip unit with LSI curves: long-time pickup Ir adjustable 160–400 A, short-time pickup Isd 1.5–10 x Ir, and instantaneous Ii fixed at 10 x In.

The 55 kA Icu at 415 V places this breaker in the M breaking capacity class — sized for industrial distribution panels where fault currents can exceed 25 kA but stay below the 70 kA+ range of the H class. The ETU350 LSI trip gives selective coordination downstream: the adjustable short-time delay (Isd) lets you ride through motor inrush without nuisance tripping, while the instantaneous (Ii) at 10 x In provides fast clearing for bolted faults. The undervoltage release (208–230 V AC) automatically opens the breaker on loss of control voltage — common in emergency-stop chains or undervoltage protection schemes on conveyor and pump panels.

Integration notes

Mounts in a standard IEC frame 400 footprint — compatible with Siemens 3VA2 busbar systems and panel-mounting kits. The auxiliary switch and trip alarm share the same wiring channel; verify the changeover contact assignment against the panel schematic before energizing. The undervoltage release coil draws continuous current when the breaker is closed and the control voltage is present — factor that into the 24 VDC or 230 VAC control transformer sizing.

Frequently asked questions

How do I get pricing and availability for 3VA2340-5HN32-0DJ0?

Submit an RFQ through this listing; the part is sourced to order via independent distribution, and current pricing and availability are confirmed at quote time.

What is the breaking capacity of this breaker?

The 3VA2340-5HN32-0DJ0 carries an Icu of 55 kA at 415 V AC, which is the M breaking capacity class in the Siemens 3VA2 range.

What trip unit and protection functions does it have?

It uses an ETU350 electronic trip unit with LSI protection: long-time pickup Ir adjustable 160–400 A, short-time pickup Isd 1.5–10 x Ir, and instantaneous Ii fixed at 10 x In.

What accessories are included with this order code?

The unit includes an undervoltage release (208–230 V AC 50/60 Hz), a nut keeper kit, one auxiliary switch (changeover H), and one trip alarm switch (changeover).

MPN
3VA2340-5HN32-0DJ0