Line protection MCCB, 400 A frame, 4-pole
At 415 VAC the interrupt rating holds at 121 kA, so it handles industrial 400 V distribution without cascading upstream breakers in most configurations.
Breaking capacity by voltage level
This MCCB delivers 187 kA at 240 VAC, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 7.5 kA at 690 V.
Panel fit and auxiliary configuration
The breaker ships without an undervoltage release or ground-fault monitoring module; those are field-addable options if the application requires shunt-trip or GF protection. The four HQ auxiliary switches provide status feedback for PLC inputs or remote indication without needing a separate accessory.