Skip to main content
Siemens 3VA2340-5HN42-0AE0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-5HN42-0AE0 SENTRON MCCB, 400 A, 4-Pole, 187

MPN3VA2340-5HN42-0AE0

Siemens SENTRON 3VA2340-5HN42-0AE0, molded case circuit breaker, 4-pole, 400 A continuous, 187 kA at 240 VAC, 121 kA at 415 VAC.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2340-5HN42-0AE0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2340-5HN42-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2340-5HN42-0AE0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C385 A
Current at 60 °C370 A
Current at 65 °C355 A
Current at 70 °C340 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.96 W

Protection & Trip Unit

3VA2340-5HN42-0AE0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2340-5HN42-0AE0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2340-5HN42-0AE0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2340-5HN42-0AE0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2340-5HN42-0AE0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width184 mm
Depth110 mm
Height (in)9.76 in
Width (in)7.24 in
Depth (in)4.33 in

Product details

Line protection MCCB, 400 A frame, 4-pole

The Siemens SENTRON 3VA2340-5HN42-0AE0 is a 4-pole molded case circuit breaker (MCCB) rated for 400 A continuous at 40 °C, designed for line protection in distribution panels. Its 187 kA breaking capacity at 240 VAC gives substantial fault-current headroom for service-entrance or main feeder applications where available short-circuit current runs high. At 415 VAC the interrupt rating holds at 121 kA, so it handles industrial 400 V distribution without cascading upstream breakers in most configurations. The 400 A frame carries full rated current through 50 °C ambient; above that it derates linearly to 340 A at 70 °C. That thermal curve matters when the breaker sits in a crowded enclosure with other heat sources — the 96 W maximum power loss at rated load adds to the internal heat rise, so panel builders should account for it in the thermal budget.

Breaking capacity by voltage level

This MCCB delivers 187 kA at 240 VAC, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 7.5 kA at 690 V. The steep drop at 690 V is typical for a 400 A frame — the arc energy at that voltage limits what a compact interrupter can clear. For 690 V feeders, confirm the available fault current stays under 7.5 kA or step to a higher-frame breaker.

Panel fit and auxiliary configuration

Dimensions are 248 mm high, 184 mm wide, 110 mm deep — a standard 4-pole MCCB footprint that drops into SENTRON mounting plates and DIN-rail adapters. The breaker ships without an undervoltage release or ground-fault monitoring module; those are field-addable options if the application requires shunt-trip or GF protection. The four HQ auxiliary switches provide status feedback for PLC inputs or remote indication without needing a separate accessory.

Frequently asked questions

Where can I buy 3VA2340-5HN42-0AE0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ to receive a firm price and lead-time estimate.

What is the breaking capacity of this MCCB at 415 V?

At 415 VAC the interrupting rating is 121 kA, matching the 440 V rating. At 240 VAC it reaches 187 kA.

What auxiliary switches are fitted on this variant?

This -0AE0 suffix includes four HQ auxiliary switches factory-installed. No undervoltage release or ground-fault monitoring is included.

MPN
3VA2340-5HN42-0AE0