Specifications

3VA2340-5JP32-0CC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2340-5JP32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2340-5JP32-0CC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C375 A
Current at 60 °C350 A
Current at 65 °C325 A
Current at 70 °C300 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.98.5 W
3VA2340-5JP32-0CC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2340-5JP32-0CC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2340-5JP32-0CC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2340-5JP32-0CC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2340-5JP32-0CC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

It carries a breaking capacity of 187 kA at 240 V and 121 kA at 415 V and 440 V, tapering to 7.5 kA at 690 V — that means it can safely interrupt massive fault currents at common distribution voltages without the arc escaping the case.

Above that it derates linearly: 375 A at 55 °C, 350 A at 60 °C, 325 A at 65 °C, and 300 A at 70 °C — the maximum operating temperature. Minimum operating temperature is -25 °C. If you're packing this into a hot panel next to transformers or drives, the 55 °C derating point is the one to watch.

Built-in accessories and communication

It also includes a communication function, so it can talk to a PLC or BMS for remote trip indication and load monitoring. Power loss at full rated current is 98.5 W, worth factoring into panel ventilation calcs.

The case dimensions are 248 mm tall, 138 mm wide, and 110 mm deep.

Frequently asked questions

How do I get current pricing and availability for 3VA2340-5JP32-0CC0?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time; we source through independent distribution and can provide current lead times on request.

What is the breaking capacity of this MCCB at 415 V?

121 kA at 415 V, same as at 440 V. At 240 V it reaches 187 kA, and at 690 V it drops to 7.5 kA.

What are the physical dimensions of 3VA2340-5JP32-0CC0?

248 mm tall, 138 mm wide, and 110 mm deep. The 110 mm depth is the critical clearance dimension for enclosure selection.

Does this breaker include communication capability?

Yes, it has a communication function for remote monitoring and trip indication, plus an undervoltage release and two HQ auxiliary switches built in.