Siemens 3VA2340-5JP32-0KA0 SENTRON MCCB, 400 A, 3-Pole

MPN3VA2340-5JP32-0KA0

Siemens SENTRON 3VA2340-5JP32-0KA0, molded case circuit breaker, 3-pole, 400 A continuous, line protection, shunt trip release, 110 x 138 x 248 mm.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2340-5JP32-0KA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2340-5JP32-0AA0

Ratings

3VA2340-5JP32-0KA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C375 A
Current at 60 °C350 A
Current at 65 °C325 A
Current at 70 °C300 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.96 W

Protection & Trip Unit

3VA2340-5JP32-0KA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2340-5JP32-0KA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2340-5JP32-0KA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2340-5JP32-0KA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2340-5JP32-0KA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

The Siemens SENTRON 3VA2340-5JP32-0KA0 is a 3-pole molded case circuit breaker rated for 400 A continuous current, designed for line protection in distribution panels. It carries a shunt trip release (STL) for remote tripping and includes a communication function for integration into monitored systems.

Breaking capacity and SCCR

The interrupting ratings span the voltage range: 187 kA at 240 V, 121 kA at both 415 V and 440 V, 75.6 kA at 500 V, and 7.5 kA at 690 V. That 187 kA at 240 V means this breaker handles high-fault scenarios on the low-voltage side without cascading upstream — useful for transformer secondaries or large busway feeds.

Thermal derating

The breaker holds its full 400 A rating from 40 °C up to 50 °C. Above that, it derates linearly: 375 A at 55 °C, 350 A at 60 °C, 325 A at 65 °C, and 300 A at 70 °C. If your panel ambient runs hot — say, a packed enclosure with drives — plan for that 300 A floor at 70 °C rather than the nameplate 400 A.

Physical fit and mounting

Dimensions are 248 mm high, 138 mm wide, and 110 mm deep. That 110 mm depth is the critical dimension for shallow enclosures or gland-plate clearance — measure your backpan depth before committing the BOM line. The 138 mm width is standard for a 3-pole MCCB in this class; it occupies one full module on the DIN rail.

Frequently asked questions

What is the breaking capacity of 3VA2340-5JP32-0KA0 at 240 V?

The interrupting rating is 187 kA at 240 V, which covers high-fault scenarios common on transformer secondaries or large busway feeds.

Where can I buy 3VA2340-5JP32-0KA0?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

MPN