Skip to main content
Siemens 3VA2340-5JQ32-0DA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-5JQ32-0DA0 SENTRON MCCB, 400 A, 3-Pole, Line

MPN3VA2340-5JQ32-0DA0

Siemens SENTRON 3VA2340-5JQ32-0DA0, 3-pole molded case circuit breaker, 400 A rated continuous current, line protection with ETU560 electronic trip unit, 187 kA at 240 V, 121 kA at 415 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2340-5JQ32-0DA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2340-5JQ32-0AA0

Ratings

3VA2340-5JQ32-0DA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C375 A
Current at 60 °C350 A
Current at 65 °C325 A
Current at 70 °C300 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V17 kA
Power loss, max.98.5 W

Protection & Trip Unit

3VA2340-5JQ32-0DA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560

Construction & Connection

3VA2340-5JQ32-0DA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2340-5JQ32-0DA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2340-5JQ32-0DA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2340-5JQ32-0DA0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

The Siemens SENTRON 3VA2340-5JQ32-0DA0 is a 3-pole molded case circuit breaker rated for 400 A continuous current, built around the ETU560 electronic trip unit for line protection. It carries a 187 kA interrupting capacity at 240 V and 121 kA at 415 V — numbers that tell you this breaker handles high-fault utility feeds without cascading upstream. The 800 V rated insulation voltage gives it headroom for 480 V and 600 V class systems common in North American and European industrial panels.

Ratings and what they mean for the panel

Rated continuous current holds at 400 A up to 50 °C ambient — that's the full frame rating without derating in a typical ventilated enclosure. Above that it steps down: 375 A at 55 °C, 350 A at 60 °C, 325 A at 65 °C, and 300 A at 70 °C. If your panel runs hot near the top of the gland plate, factor the 55 °C or 60 °C row into the BOM, not the 400 A nameplate. Interrupting capacity drops with system voltage: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V. That 17 kA at 690 V is the number to check if this breaker lands on a 690 V mining or marine distribution bus — it's still adequate for most downstream subfeeds but not for a main with high fault current. The ETU560 electronic trip unit provides adjustable long-time, short-time, instantaneous, and ground-fault protection curves. Ground-fault monitoring uses summation current formation on the L-conductor — it detects leakage without a separate neutral CT. Communication function is built in, so the breaker can report status and trip events over the plant network without an add-on module.

Panel fit and integration

Dimensions are 248 mm high, 138 mm wide, 110 mm deep. Mounts on a DIN rail or direct panel-mount via the base. No auxiliary contact version is fitted from the factory, but the slot accepts the 3VA9608-0BB25 auxiliary trip if you need remote status later. Power loss at full load is 98.5 W maximum — that's the heat you need to vent. In a multi-breaker lineup, sum the losses and size the enclosure ventilation accordingly. Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C, so it can sit in an unheated warehouse through winter without damage.

Frequently asked questions

Will 3VA2340-5JQ32-0DA0 drop into a panel specified around 3VA1112-5EF32-0CA0?

The 3VA2340-5JQ32-0DA0 is a larger frame (400 A vs the smaller 3VA1 frame) with different dimensions and a higher interrupting capacity. It will not physically drop into the same mounting footprint or busbar arrangement without panel rework. Check the 3VA1 frame if the original spec called for a lower-current MCCB.

MPN
3VA2340-5JQ32-0DA0