Skip to main content
Siemens 3VA2340-5JQ32-0JL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-5JQ32-0JL0 SENTRON MCCB, 400 A, 187 kA at 24

MPN3VA2340-5JQ32-0JL0

Siemens SENTRON 3VA2340-5JQ32-0JL0, molded case circuit breaker, 3-pole, 400 A, 187 kA at 240 V, ETU560 electronic trip unit, line protection.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2340-5JQ32-0JL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2340-5JQ32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22
3VA2340-5JQ32-0JL0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C375 A
Current at 60 °C350 A
Current at 65 °C325 A
Current at 70 °C300 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V17 kA
Power loss, max.96 W
3VA2340-5JQ32-0JL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560
3VA2340-5JQ32-0JL0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2340-5JQ32-0JL0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4
3VA2340-5JQ32-0JL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2340-5JQ32-0JL0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

400 A MCCB with 187 kA interrupting capacity — selectivity anchor for high-fault panels

Its headline interrupting ratings — 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V — mean this breaker can clear a bolted fault at those levels without rupturing, which is the deciding factor for main or feeder positions in high-capacity distribution switchboards where upstream transformer impedance is low. It does not include an undervoltage release or phase failure detection, so those functions must be added externally if required.

Rated at 400 A from 40 °C through 50 °C ambient, the breaker derates to 375 A at 55 °C, 350 A at 60 °C, 325 A at 65 °C, and 300 A at 70 °C. The 110 mm depth, 138 mm width, and 248 mm height fit standard MCCB mounting footprints; verify the busbar connection centers against the existing panel layout. Maximum power loss is 96 W, which contributes to the enclosure heat load — account for this when sizing ventilation or cooling for a multi-breaker lineup.

Frequently asked questions

Where can I buy 3VA2340-5JQ32-0JL0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ to receive a firm price and lead-time confirmation.

What is the breaking capacity of 3VA2340-5JQ32-0JL0 at different voltages?

187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V — these ratings govern its use as a main or feeder breaker in high-fault-capacity systems.

What is the continuous current rating and how does it derate with temperature?

Rated 400 A continuous from 40 °C to 50 °C ambient. Derates to 375 A at 55 °C, 350 A at 60 °C, 325 A at 65 °C, and 300 A at 70 °C.

What trip unit does this breaker use?

It uses the ETU560 electronic trip unit, which provides adjustable long-time, short-time, instantaneous, and ground-fault protection curves.

MPN