The 400 A rating holds from 40 °C through 50 °C; above that it derates to 375 A at 55 °C, 350 A at 60 °C, 325 A at 65 °C, and 300 A at 70 °C.
Breaking capacity by voltage — where it fits
At 500 V the breaker still clears 75.6 kA; at 690 V it drops to 7.5 kA.
The breaker measures 184 mm wide, 248 mm tall, and 110 mm deep — a 4-pole frame that occupies standard MCCB panel space.