Skip to main content
Siemens 3VA2340-5JQ42-0KC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-5JQ42-0KC0 SENTRON MCCB, 400A, 4P, 187kA

MPN3VA2340-5JQ42-0KC0

Siemens SENTRON 3VA2340-5JQ42-0KC0, molded case circuit breaker, 4-pole, 400 A rated continuous current, breaking capacity 187 kA at 240 V, line protection version with ETU560 electronic trip unit.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2340-5JQ42-0KC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2340-5JQ42-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2340-5JQ42-0KC0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C375 A
Current at 60 °C350 A
Current at 65 °C325 A
Current at 70 °C300 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V17 kA
Power loss, max.96 W
3VA2340-5JQ42-0KC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560
3VA2340-5JQ42-0KC0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2340-5JQ42-0KC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2340-5JQ42-0KC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2340-5JQ42-0KC0 — Mechanical
ParameterValue
Height248 mm
Width184 mm
Depth110 mm

Product details

SENTRON 3VA2340-5JQ42-0KC0 — 400 A MCCB with ETU560, 4-Pole, Active Production

The Siemens SENTRON 3VA2340-5JQ42-0KC0 is a 4-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current Iu of 400 A at 40 °C with an insulation voltage Ui of 800 V. Communication functionality is built in, enabling integration with higher-level control systems.

Breaking capacity varies sharply with system voltage: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V. These figures cover most low-voltage distribution panels; the 17 kA at 690 V still handles typical industrial fault levels on 690 V networks. For selectivity coordination, the high interrupting ratings at 240–440 V allow this breaker to serve as a main or feeder device upstream of lower-rated branch breakers.

Rated 400 A from 40 °C through 50 °C ambient; above that, the continuous current derates linearly to 375 A at 55 °C, 350 A at 60 °C, 325 A at 65 °C, and 300 A at 70 °C. Power loss at full rated current is 96 W maximum — account for this in enclosure thermal calculations, especially in sealed or high-ambient cabinets.

Frequently asked questions

What is the breaking capacity of this MCCB at 415 V?

121 kA at 415 V, which matches the rating at 440 V. At 500 V it drops to 75.6 kA, and at 690 V to 17 kA.

What trip unit does this breaker use?

It uses the ETU560 electronic trip unit, which provides adjustable overcurrent protection with communication capability.

Where can I buy 3VA2340-5JQ42-0KC0?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Contact us for current availability and pricing.

MPN
3VA2340-5JQ42-0KC0