Skip to main content
Siemens 3VA2340-5KP32-0CA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-5KP32-0CA0 SENTRON MCCB, 400 A, 3-Pole

MPN3VA2340-5KP32-0CA0

Siemens SENTRON 3VA2340-5KP32-0CA0, molded case circuit breaker, 3-pole, 400 A (40 °C), ETU850 electronic release, line protection, 187 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2340-5KP32-0CA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2340-5KP32-0AA0

Ratings

3VA2340-5KP32-0CA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C375 A
Current at 60 °C350 A
Current at 65 °C325 A
Current at 70 °C300 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.98.5 W

Protection & Trip Unit

3VA2340-5KP32-0CA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
Overcurrent protection functionLSI
Ground-fault monitoringWithout

Construction & Connection

3VA2340-5KP32-0CA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2340-5KP32-0CA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2340-5KP32-0CA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2340-5KP32-0CA0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

What the ratings mean for fit

The Siemens SENTRON 3VA2340-5KP32-0CA0 is a 3-pole molded case circuit breaker rated for 400 A continuous at 40 °C, with a slight thermal derating curve: it holds 375 A at 55 °C and 300 A at 70 °C — so if your panel runs hot near the top of the enclosure, you need to account for that drop in the BOM. The interrupting ratings are hefty: 187 kA at 240 V, 121 kA at 415 V and at 440 V, then 75.6 kA at 500 V, and 7.5 kA at 690 V. That kind of short-circuit capacity tells you this breaker is sized for high-fault infrastructure — main feeders, large motor control centers, or transformer secondaries — where the available fault current is serious. The ETU850 electronic release gives you adjustable long-time, short-time, and instantaneous pickup, plus ground-fault alarm (not trip) capability; the undervoltage release (fitted) lets you drop the breaker on loss of control power, common in safety circuits. There's no auxiliary contact on this variant, so if you need status feedback to a PLC, plan on adding one separately.

Panel fit and integration

The breaker measures 138 mm wide by 248 mm tall by 110 mm deep. The front face carries IP40 protection. It includes a communication function.

Frequently asked questions

Does this breaker include a trip indicator or auxiliary contacts?

No. This variant has no trip indicator and no auxiliary contact version. It does include an undervoltage release and a communication function.

MPN
3VA2340-5KP32-0CA0