Siemens 3VA2340-5KP32-0CL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-5KP32-0CL0 SENTRON MCCB, 400 A, 3-Pole, 121

MPN3VA2340-5KP32-0CL0

Siemens SENTRON 3VA2340-5KP32-0CL0, molded case circuit breaker, 3-pole, 400 A, 121 kA at 415 V, line protection with undervoltage release and communication function.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2340-5KP32-0CL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2340-5KP32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22
3VA2340-5KP32-0CL0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C375 A
Current at 60 °C350 A
Current at 65 °C325 A
Current at 70 °C300 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.98.5 W
3VA2340-5KP32-0CL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2340-5KP32-0CL0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2340-5KP32-0CL0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts4
3VA2340-5KP32-0CL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2340-5KP32-0CL0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

It's designed as a line protection device — meaning it sits at the main incoming feed or large subfeed, not on individual motor circuits. That's a real panel-space saver.

Dimensions are 248 mm high by 138 mm wide by 110 mm deep — it'll fit a standard MCCB slot in most SENTRON or third-party distribution panels. No derating up to 50 °C at full 400 A, which is solid for a warm enclosure. That thermal curve is what you check when the panel sits next to a furnace line or in a non-climate-controlled electrical room.

Frequently asked questions

Does this breaker include an undervoltage release?

Yes, the 3VA2340-5KP32-0CL0 comes with an undervoltage release (UVR) as standard equipment. It also includes two auxiliary switches, one trip alarm switch, and one electrical alarm switch.

MPN