Siemens 3VA2340-5KP32-0DA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-5KP32-0DA0 SENTRON MCCB, 400 A, 187 kA at 24

MPN3VA2340-5KP32-0DA0

Siemens SENTRON 3VA2340-5KP32-0DA0, molded case circuit breaker, 3-pole, 400 A, 187 kA at 240 V, ETU850, UVR, 110 x 138 x 248 mm.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2340-5KP32-0DA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2340-5KP32-0AA0

Ratings

3VA2340-5KP32-0DA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C375 A
Current at 60 °C350 A
Current at 65 °C325 A
Current at 70 °C300 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V17 kA
Power loss, max.98.5 W

Protection & Trip Unit

3VA2340-5KP32-0DA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850

Construction & Connection

3VA2340-5KP32-0DA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2340-5KP32-0DA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2340-5KP32-0DA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2340-5KP32-0DA0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

Line protection with ETU850 — 400 A continuous, 187 kA interrupting

The Siemens SENTRON 3VA2340-5KP32-0DA0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection duty. It carries a rated continuous current Iu of 400 A at 40 °C and holds the full 400 A through 50 °C before derating begins — at 55 °C it's 375 A, at 65 °C it's 325 A, and at 70 °C it's 300 A. The interrupting capacity reaches 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V. That 187 kA at 240 V figure is the headline — it clears very high available fault currents typical in large distribution switchboards without cascading upstream breakers. The overcurrent release is an ETU850 electronic trip unit. Communication function is present on this variant, and an undervoltage release (UVR) is integrated — designated as 3VA9608-0BB25 for the auxiliary trip component. The rated insulation voltage Ui is 800 V. Maximum power loss is 98.5 W. This is a current-production part (lifecycle stage marked as active). It's sourced to order against an RFQ through independent distribution channels — pricing and availability confirmed at quote time.

Integration into a panel — dimensions and mounting

Physical footprint: 138 mm wide, 248 mm high, 110 mm deep. The 138 mm width is the standard 3-pole MCCB form factor for this SENTRON frame — it occupies three adjacent 45 mm-wide module positions on a DIN rail or panel-mount plate. The 110 mm depth means it fits within a 200 mm deep enclosure with clearance for rear busbars and wiring gutters. No auxiliary contact version is fitted on this order code (the slot is available). Trip indicator is not present on the front bezel — the ETU850 display provides fault indication via the communication interface. Phase failure detection is not a function of this release; it relies on the ETU's internal algorithms for phase imbalance.

Environmental limits and storage

Operating temperature range is -25 °C to 70 °C. Storage range is wider: -40 °C to 80 °C, which governs handling during shipping and warehouse staging, not running duty. The latching endurance is rated at 15,000 operations — this is the mechanical life under normal switching, not short-circuit fault interruption.

Frequently asked questions

What are the key ratings for 3VA2340-5KP32-0DA0?

400 A continuous at 40 °C, 187 kA interrupting at 240 V, 121 kA at 415 V, ETU850 electronic trip unit, 800 V rated insulation voltage. Dimensions: 138 x 248 x 110 mm.

Where can I buy 3VA2340-5KP32-0DA0 and get current pricing?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

Will 3VA2340-5KP32-0DA0 drop into a panel specified around 5SQ2370-2YA05 without rewiring?

The 3VA2340-5KP32-0DA0 is a SENTRON frame MCCB with a 138 mm width and 110 mm depth. The 5SQ2370-2YA05 is a different manufacturer's device. Panel fit depends on busbar spacing, lug type, and mounting hole pattern — physical interchangeability is not guaranteed. A panel re-evaluation is recommended.

MPN
3VA2340-5KP32-0DA0