Skip to main content
Siemens 3VA2340-5KP32-0DH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-5KP32-0DH0 SENTRON MCCB, 400 A, Adjustable 6

MPN3VA2340-5KP32-0DH0

Siemens SENTRON 3VA2340-5KP32-0DH0, molded case circuit breaker, 3-pole, 400 A continuous, adjustable trip 600–4000 A, 187 kA at 240 V, line protection design with undervoltage release and auxiliary switches.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2340-5KP32-0DH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2340-5KP32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2340-5KP32-0DH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C375 A
Current at 60 °C350 A
Current at 65 °C325 A
Current at 70 °C300 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.98.5 W

Protection & Trip Unit

3VA2340-5KP32-0DH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2340-5KP32-0DH0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2340-5KP32-0DH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2340-5KP32-0DH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2340-5KP32-0DH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

Siemens 3VA2340-5KP32-0DH0 — SENTRON MCCB, 400 A, Line Protection with Communication

The Siemens SENTRON 3VA2340-5KP32-0DH0 is a 3-pole molded case circuit breaker (MCCB) rated for 400 A continuous current at 40 °C, with an adjustable thermal-magnetic trip unit covering 600 A to 4000 A — meaning the same breaker body can be dialled in for a 600 A feeder or a 4000 A main, depending on the load study. At 240 V it interrupts 187 kA; at 415 V / 440 V it holds 121 kA, and at 690 V the interrupting rating drops to 7.5 kA, so the available fault current at the installation point must be verified against the voltage-specific curve. The line-protection design targets main incomers and large feeders, not branch motor circuits. Built-in communication and other measurement functions allow integration into a plant monitoring system — the exact protocol is set by the plug-in communication module (not included in this base order code).

Temperature Derating & Continuous Current

The 400 A rating holds up to 50 °C ambient. Above that the breaker must be derated: 375 A at 55 °C, 350 A at 60 °C, 325 A at 65 °C, and 300 A at 70 °C (–). If the panel ambient runs hot — say a non-climate-controlled enclosure near a furnace line — use the 55 °C or 60 °C column to size the load. The maximum operating temperature is 70 °C; storage range is -40 °C to 80 °C (–).

Auxiliary Switches & Undervoltage Release

This variant ships with two auxiliary switches plus one trip alarm switch (HQ type) — enough for remote status and alarm annunciation without an external relay. It also includes an undervoltage release (UVR) that trips the breaker when control voltage drops below a threshold, standard for safety interlocks or emergency-stop chains. The basic switch assembly is order code 3VA2340-5KP32-0AA0; the UVR and aux switches are factory-integrated, not field-addable on this SKU.

Dimensions & Panel Fit

Footprint: 138 mm wide × 248 mm high × 110 mm deep (–). That 110 mm depth (4.33 in) is shallow for a 400 A frame — fits in a 250 mm deep enclosure with room for rear cable lugs. Width of 138 mm (5.43 in) means a 3-pole unit occupies about 5.5 module spaces on a DIN rail; plan the backpanel layout accordingly.

Frequently asked questions

Where can I buy 3VA2340-5KP32-0DH0 and how is it quoted for volume?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the interrupting rating at 415 V?

At 415 V the interrupting rating is 121 kA. The same rating applies at 440 V; at 500 V it drops to 75.6 kA, and at 690 V to 7.5 kA (–).

What compliance documentation does Siemens provide for this breaker?

The SENTRON 3VA series is typically certified to IEC 60947-2 and carries UL/CSA listings where applicable. RoHS and REACH declarations are available from Siemens' documentation portal. The specific certification marks for this order code should be verified against the factory certificate.

MPN