Siemens 3VA2340-5KP32-0JL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-5KP32-0JL0 SENTRON MCCB, 400 A, 3-Pole, 187

MPN3VA2340-5KP32-0JL0

Siemens SENTRON 3VA2340-5KP32-0JL0, molded case circuit breaker, 3-pole, 400 A continuous rating, 187 kA interrupting at 240 V, line protection design with communication function.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2340-5KP32-0JL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2340-5KP32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22

Ratings

3VA2340-5KP32-0JL0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C375 A
Current at 60 °C350 A
Current at 65 °C325 A
Current at 70 °C300 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.96 W

Protection & Trip Unit

3VA2340-5KP32-0JL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2340-5KP32-0JL0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2340-5KP32-0JL0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2340-5KP32-0JL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2340-5KP32-0JL0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

The Siemens SENTRON 3VA2340-5KP32-0JL0 is a 3-pole molded case circuit breaker (MCCB) rated for 400 A continuous current, designed for line protection in distribution panels. Its interrupting capacity reaches 187 kA at 240 V and 121 kA at 415 V and 440 V, dropping to 75.6 kA at 500 V and 7.5 kA at 690 V — the 690 V figure is the one to watch if your system runs at that voltage; it's still adequate for most industrial service-entrance applications but coordination studies need to confirm selectivity at the lower end.

Thermal derating and panel fit

The breaker holds its full 400 A rating up to 50 °C ambient; above that it derates linearly to 375 A at 55 °C, 350 A at 60 °C, 325 A at 65 °C, and 300 A at 70 °C. If your panel runs hot — say a non-ventilated enclosure near a furnace line — size the load side for the derated figure, not the nameplate. Dimensions are 248 mm high, 138 mm wide, 110 mm deep, which fits standard Siemens SENTRON mounting footprints; the 110 mm depth is shallow enough for most 400 mm deep enclosures without forcing a deeper can.

Auxiliaries and communication

This variant ships with a shunt trip release (STL) and a full auxiliary switch complement: 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch (HQ configuration). It also includes a voltage trigger and a communication function — likely for remote monitoring or integration with a higher-level energy management system. No undervoltage release is fitted, so if your safety circuit requires UVR for machine isolation, you'll need to add it externally or spec a different variant. The supplied basic switch is order code 3VA2340-5KP32-0AA0, which is the core breaker without auxiliaries.

Frequently asked questions

What is the closest functional second-source to 3VA2340-5KP32-0JL0?

A direct drop-in replacement within the same SENTRON 3VA family would be a 3VA2 frame with the same 400 A continuous rating and 3-pole configuration, but the exact auxiliary and trip unit configuration differs — verify the shunt trip and communication functions match your BOM before substituting.

Will 3VA2340-5KP32-0JL0 drop into a panel specified around a smaller 3VA2 frame breaker?

The 248 mm height and 138 mm width match the standard SENTRON 3VA2 frame footprint, so it will physically fit the same mounting holes and bus connections as other 3VA2 breakers. The 110 mm depth is also consistent. No rewiring of the bus bars should be needed, but verify the lug kit matches your cable size.

MPN
3VA2340-5KP32-0JL0