Siemens 3VA2340-6HL32-0AB0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-6HL32-0AB0 SENTRON MCCB, 400 A, 242 kA at 24

MPN3VA2340-6HL32-0AB0

Siemens SENTRON 3VA2340-6HL32-0AB0, molded case circuit breaker, 3-pole, 400 A, interrupting rating 242 kA at 240 V, ETU320 electronic trip unit, 2 auxiliary switches HP.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2340-6HL32-0AB0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2340-6HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA11

Ratings

3VA2340-6HL32-0AB0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C385 A
Current at 60 °C370 A
Current at 65 °C355 A
Current at 70 °C340 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.96 W

Protection & Trip Unit

3VA2340-6HL32-0AB0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout

Construction & Connection

3VA2340-6HL32-0AB0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2340-6HL32-0AB0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2340-6HL32-0AB0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2340-6HL32-0AB0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

What this MCCB delivers

The Siemens SENTRON 3VA2340-6HL32-0AB0 is a 3-pole molded case circuit breaker rated 400 A continuous at 40 °C, with an interrupting capacity of 242 kA at 240 V — enough to handle high-fault utility feeds or transformer secondaries without cascading upstream. The ETU320 electronic trip unit gives you adjustable long-time, short-time, and instantaneous protection curves, so you can coordinate selectively downstream. Two HP auxiliary switches are built in for status feedback to the PLC or panel indication.

Ratings that matter for panel fit

At 415 V and 440 V the interrupting rating holds at 187 kA; at 690 V it drops to 7.5 kA — still adequate for most 690 V motor circuits but not for high-fault 690 V mains. The continuous current derates above 55 °C: 385 A at 55 °C, 370 A at 60 °C, 355 A at 65 °C, 340 A at 70 °C. If your enclosure ambient runs hot, size the breaker for the actual temperature, not the 400 A nameplate. Rated insulation voltage is 800 V, so it's comfortable on 480 V and 600 V class systems.

Physical integration

Dimensions: 248 mm high, 138 mm wide, 110 mm deep. It mounts on a DIN rail or panel-mount plate inside a standard enclosure. The 110 mm depth leaves room for rear-access wiring in a 300 mm deep cabinet. No undervoltage release, no shunt trip, no communication module on this variant — it's a straight line-protection breaker with auxiliary contacts only.

Frequently asked questions

How do I get current pricing and availability for 3VA2340-6HL32-0AB0?

Submit an RFQ through this listing. We source through independent distribution and confirm price and lead time at quote time — no stock figures or prices are published here.

What is the interrupting rating of this MCCB at 240 V?

242 kA at 240 V, which covers high-fault utility feeds and transformer secondaries without needing a current-limiting fuse upstream.

What trip unit does the 3VA2340-6HL32-0AB0 use?

It uses the ETU320 electronic trip unit, offering adjustable long-time, short-time, and instantaneous protection for selective coordination.

Will 3VA2340-6HL32-0AB0 drop into a panel specified around 3VA1110-5EF36-0AD0?

No — the 3VA1110 is a smaller-frame breaker with different mounting dimensions and a lower continuous rating. The 3VA2340 is physically larger (248 x 138 x 110 mm) and requires its own panel cutout or DIN-rail space.