Skip to main content
Siemens 3VA2340-6HL32-0JH0 — Molded Case Circuit Breakers (MCCB)

3VA2340-6HL32-0JH0 SENTRON MCCB, 400 A, 3-pole, 242 kA at 24

MPN3VA2340-6HL32-0JH0

Siemens SENTRON 3VA2340-6HL32-0JH0, molded case circuit breaker, 3-pole, 400 A rated current, 242 kA breaking capacity at 240 V AC, line protection design, with shunt trip and auxiliary switches.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2340-6HL32-0JH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2340-6HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA2340-6HL32-0JH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C385 A
Current at 60 °C370 A
Current at 65 °C355 A
Current at 70 °C340 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.96 W
3VA2340-6HL32-0JH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2340-6HL32-0JH0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2340-6HL32-0JH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA2340-6HL32-0JH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2340-6HL32-0JH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

The Siemens SENTRON 3VA2340-6HL32-0JH0 is a 3-pole molded case circuit breaker rated for 400 A continuous current across the 40 °C to 50 °C ambient range — no derating needed in a standard 40 °C panel environment. At 415 V and 440 V it still holds 187 kA, dropping to 121 kA at 500 V and 7.5 kA at 690 V — the steep roll-off above 500 V means this breaker is primarily sized for 240–500 V distribution, not 690 V motor circuits. The basic switch assembly is order code 3VA2340-6HL32-0AA0 — the -0JH0 suffix adds the shunt trip and auxiliary contact block. Maximum power loss is 96 W — plan for that heat rejection inside the enclosure if the breaker is loaded near its 400 A rating continuously.

Thermal derating curve — where the 400 A rating holds and where it drops

At 55 °C it derates to 385 A, at 60 °C to 370 A, at 65 °C to 355 A, and at 70 °C to 340 A.

Physical fit — panel integration notes

The 138 mm width across three poles means a 4-pole version of the same frame would be roughly 184 mm. Mounting is via the rear panel or DIN rail adapter (not included in this variant). Allow the 96 W dissipation in the thermal budget; forced ventilation may be needed if the enclosure is sealed and loaded continuously.

Frequently asked questions

What is the breaking capacity of 3VA2340-6HL32-0JH0 at different voltages?

At 240 V it interrupts 242 kA, at 415 V and 440 V it interrupts 187 kA, at 500 V it interrupts 121 kA, and at 690 V it interrupts 7.5 kA. The steep drop above 500 V means this breaker is best suited for 240–500 V distribution.

Where can I buy 3VA2340-6HL32-0JH0 and how is it quoted?

This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — no stock figures or lead-time numbers are published here.

What are the physical dimensions of 3VA2340-6HL32-0JH0?

Height is 248 mm, width is 138 mm, and depth is 110 mm — a standard MCCB footprint for the 400 A class.

Does 3VA2340-6HL32-0JH0 include a shunt trip or auxiliary contacts?

Yes, it includes a shunt trip release (STL), two auxiliary switches, and one trip alarm switch HQ. The basic switch assembly is order code 3VA2340-6HL32-0AA0; the -0JH0 suffix adds the shunt trip and auxiliary block.

MPN
3VA2340-6HL32-0JH0