Skip to main content
Siemens 3VA2340-6HN32-0CL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-6HN32-0CL0 SENTRON MCCB, 400 A, 3-Pole, Line

MPN3VA2340-6HN32-0CL0

Siemens SENTRON 3VA2340-6HN32-0CL0, molded case circuit breaker, 3-pole, 400 A rated continuous current Iu, ETU350 electronic trip unit, line protection version, 242 kA breaking capacity at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2340-6HN32-0CL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2340-6HN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22

Ratings

3VA2340-6HN32-0CL0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C385 A
Current at 60 °C370 A
Current at 65 °C355 A
Current at 70 °C340 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V40 kA
Power loss, max.98.5 W

Protection & Trip Unit

3VA2340-6HN32-0CL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350

Construction & Connection

3VA2340-6HN32-0CL0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2340-6HN32-0CL0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2340-6HN32-0CL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2340-6HN32-0CL0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

What this 400 A MCCB delivers for a main feeder

The Siemens 3VA2340-6HN32-0CL0 is a 3-pole SENTRON molded case circuit breaker rated for 400 A continuous current (Iu) with an ETU350 electronic trip unit, built for line protection in distribution panels. At 240 V it interrupts 242 kA, and the rating holds at 187 kA through 415 V and 440 V, then steps to 121 kA at 500 V and 40 kA at 690 V — that kind of headroom means it handles high-fault service entrances without cascading upstream. The 400 A rating stays flat from 40 °C up to 50 °C; above that it derates linearly, hitting 340 A at 70 °C, so the thermal curve is predictable for a warm panel.

Trip unit and auxiliary complement

The ETU350 is a programmable electronic trip unit that supports LSIG (long-time, short-time, instantaneous, ground-fault) protection profiles, though this specific variant ships without a ground-fault monitoring module. It includes an undervoltage release (UVR) for coordinated shutdown sequences. The auxiliary contact block is loaded: 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch (HQ type), which gives the controls engineer a clean set of status signals back to the PLC without adding a separate module.

Panel fit and environmental limits

Dimensions are 248 mm high, 138 mm wide, and 110 mm deep — it mounts on a DIN rail or directly to a backplate in a standard MCCB footprint. Operating temperature range is -25 °C to 70 °C, storage from -40 °C to 80 °C. Maximum power dissipation is 98.5 W, so factor that into your enclosure thermal budget if it's in a sealed cabinet with other high-current devices. Rated insulation voltage is 800 V, keeping it comfortable on 480/600 V systems with margin.

Frequently asked questions

What is the breaking capacity of 3VA2340-6HN32-0CL0 at 240 V?

It is rated 242 kA at 240 V, with 187 kA at 415 V and 440 V, 121 kA at 500 V, and 40 kA at 690 V.

Where can I buy 3VA2340-6HN32-0CL0?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What trip unit does the 3VA2340-6HN32-0CL0 use?

It uses the ETU350 electronic trip unit, configured for line protection without ground-fault monitoring, and includes an undervoltage release.

MPN