Skip to main content
Siemens 3VA2340-6HN32-0HA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-6HN32-0HA0 SENTRON MCCB, 400 A, 3-Pole, Shun

MPN3VA2340-6HN32-0HA0

Siemens SENTRON 3VA2340-6HN32-0HA0, molded case circuit breaker, 3-pole, 400 A, line protection, with shunt trip (STL), breaking capacity 242 kA at 240 V AC.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2340-6HN32-0HA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2340-6HN32-0AA0

Ratings

3VA2340-6HN32-0HA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C385 A
Current at 60 °C370 A
Current at 65 °C355 A
Current at 70 °C340 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.96 W

Protection & Trip Unit

3VA2340-6HN32-0HA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2340-6HN32-0HA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2340-6HN32-0HA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2340-6HN32-0HA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2340-6HN32-0HA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

Siemens SENTRON 3VA2340-6HN32-0HA0 — 400 A MCCB with Shunt Trip

The Siemens SENTRON 3VA2340-6HN32-0HA0 is a 3-pole molded case circuit breaker (MCCB) rated for 400 A continuous current, designed for line protection in distribution panels and industrial switchgear. It carries a shunt trip release (STL) for remote tripping, making it suitable for emergency-off or interlock circuits where the breaker must open on a signal from a safety relay or PLC. Breaking capacity is 242 kA at 240 V AC, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 7.5 kA at 690 V — figures that cover most industrial service-entrance and sub-distribution applications where fault current runs high at lower voltages. The thermal derating curve holds 400 A flat from 40 °C to 50 °C, then steps down: 385 A at 55 °C, 370 A at 60 °C, 355 A at 65 °C, and 340 A at 70 °C. That means in a warm enclosure or high-ambient machine room you lose about 15 % of the rating at the top end — plan the load accordingly.

Sizing and Integration

Dimensions are 248 mm high, 138 mm wide, 110 mm deep — a standard 3-pole MCCB footprint for panelboard or enclosed switchgear mounting. The 110 mm depth (4.33 in) leaves clearance for rear-connected bus bars or cable lugs in a typical 600 mm deep enclosure. Power loss is 96 W maximum at rated load, so account for that in the enclosure thermal calculation. The shunt trip release (STL) is factory-installed; no auxiliary switch is fitted on this variant. If you need a status contact for remote indication, you'll add an auxiliary switch block (not included). The breaker has a voltage-trigger function but no undervoltage release and no ground-fault monitoring module — this is a straight line-protection device with remote-trip capability only.

Frequently asked questions

What is the breaking capacity of 3VA2340-6HN32-0HA0 at 415 V?

187 kA at 415 V AC. At 240 V it is 242 kA, at 440 V also 187 kA, at 500 V it drops to 121 kA, and at 690 V to 7.5 kA.

Does this MCCB include a shunt trip for remote opening?

Yes, it is fitted with a shunt trip release (STL) for remote tripping. No undervoltage release or ground-fault module is included.

How do I get current pricing and availability for 3VA2340-6HN32-0HA0?

Submit an RFQ through this listing. We source the part to order and confirm current pricing and lead time at quote — no automated stock figures here.

What is the continuous current rating at 50 °C?

400 A from 40 °C to 50 °C. Above that it derates: 385 A at 55 °C, 370 A at 60 °C, 355 A at 65 °C, 340 A at 70 °C.

MPN
3VA2340-6HN32-0HA0