Skip to main content
Siemens 3VA2340-6JP32-0BA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2340-6JP32-0BA0 MCCB, 400A, 3-Pole, UVR

MPN3VA2340-6JP32-0BA0

Siemens SENTRON 3VA2340-6JP32-0BA0, molded case circuit breaker, 3-pole, 400 A continuous, line protection, undervoltage release, interrupting 242 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2340-6JP32-0BA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2340-6JP32-0AA0
3VA2340-6JP32-0BA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C375 A
Current at 60 °C350 A
Current at 65 °C325 A
Current at 70 °C300 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.98.5 W
3VA2340-6JP32-0BA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2340-6JP32-0BA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2340-6JP32-0BA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2340-6JP32-0BA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2340-6JP32-0BA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

It carries an interrupting capacity of 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 7.5 kA at 690 V — covering high-fault industrial feeds and transformer secondaries.

Temperature derating and real-world current

The 400 A rating holds up to 50 °C ambient. Above that, it derates: 375 A at 55 °C, 350 A at 60 °C, 325 A at 65 °C, and 300 A at 70 °C. Size the load accordingly; a 400 A feeder in a 60 °C panel is effectively a 350 A breaker.

Frequently asked questions

What is the interrupting capacity of 3VA2340-6JP32-0BA0 at 480 V?

The evidence provides interrupting ratings at 240 V (242 kA), 415 V (187 kA), 440 V (187 kA), 500 V (121 kA), and 690 V (7.5 kA). A 480 V value is not listed; the 440 V rating (187 kA) is the nearest available figure.

Where can I buy 3VA2340-6JP32-0BA0?

This MCCB is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
3VA2340-6JP32-0BA0