Skip to main content
Siemens 3VA2340-6JP32-0DC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2340-6JP32-0DC0 SENTRON MCCB, 400 A, 3-Pole, ETU5

MPN3VA2340-6JP32-0DC0

Siemens SENTRON 3VA2340-6JP32-0DC0, molded case circuit breaker, 3-pole, 400 A, ETU550 electronic trip unit, 242 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2340-6JP32-0DC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2340-6JP32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2340-6JP32-0DC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C375 A
Current at 60 °C350 A
Current at 65 °C325 A
Current at 70 °C300 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V40 kA
Power loss, max.98.5 W
3VA2340-6JP32-0DC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
3VA2340-6JP32-0DC0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2340-6JP32-0DC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2340-6JP32-0DC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2340-6JP32-0DC0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

That 400 A holds from 40 °C through 50 °C ambient; at 55 °C it derates to 375 A, and at 70 °C it's 300 A — so if your panel runs hot, the real ampacity is lower than the nameplate. The interrupting ratings are substantial: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 40 kA at 690 V. For a main feeder or large motor branch, that means it clears high-fault events without upstream coordination headaches. It also has a communication function — the ETU550 supports data exchange over the SENTRON communication bus, so you can pull trip data and status into a PLC or BMS without adding a separate module. The max power loss is 98.5 W, which matters for enclosure thermal management if you're stacking multiple breakers.

The ETU550 trip unit is field-replaceable, and the auxiliary switches (2 HQ) are plug-in, so you can swap them without pulling the breaker.

MPN
3VA2340-6JP32-0DC0